TABLE 8 - STATIC RESISTANCES

1

TABLE 9 - POWER EXHAUST PERFORMANCE

MOTOR

SPEED

STATIC RESISTANCE OF RETURN DUCTWORK, IWG

0.2

0.3

0.4

0.5

0.6

CFM

KW

CFM

KW

CFM

KW

CFM

KW

CFM

KW

HIGH*

5250

0.83

4500

0.85

4200

0.88

3750

0.93

3000

0.99

MEDIUM

4900

0.77

3900

0.79

3500

0.82

2900

0.85

-

-

LOW

4400

0.72

3700

0.74

3000

0.78

-

-

-

-

*

Factory Setting

Power Exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.

MODEL

SIZE

DRIVE

BLOWER

RANGE

(RPM)

MOTOR

1

ADJUSTABLE MOTOR PULLEY

FIXED BLOWER PULLEY

BELT

(NOTCHED)

HP FRAME

EFF.

(%)

DESIG-

NATION

OUTSIDE

DIA.
(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

DESIG-

NATION

OUTSIDE

DIA.
(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

DESIG-

NATION

PITCH

LENGTH

(IN.)

QTY.

15 TON

Stan-

dard

850/1065

5

184T

83

1VP56

5.35

4.3-
5.3

2

1-1/8

BK90

8.75

8.4

1

BX70

71.8

1

High

Speed

Access

965/1190

BK80

7.75

7.4

1

BX68

69.8

1

20 TON

Stan-

dard

870/1025

7.5

213T

89

1VP68

6.75

5.5-
6.5

2

1-3/8

BK120

11.75

11.4 1-3/16

BX83

84.8

1

High

Speed

Access

950/1120

BK110

10.75

10.4 1-3/16

BX80

81.8

1

1

All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream

of any heating device.

2

Do NOT close this pulley below 1 turn open.

TABLE 10 - BLOWER MOTOR AND DRIVE DATA

EXTERNAL STATIC PRESSURE DROP

DESCRIPTION

RESISTANCE, IWG

CFM

15 TON

20 TON

4500

6000

7200

6000

8000

9400

WET INDOOR COIL

0.1

0.1

0.1

0.1

0.1

0.1

ELECTRIC HEAT OPTIONS

18 KW

0.1

0.1

0.1

0.1

0.1

0.1

36 KW

0.1

0.2

0.3

0.1

0.2

0.3

54 KW

0.2

0.3

0.4

0.2

0.3

0.4

72 KW

0.2

0.4

0.6

0.2

0.4

0.6

ECONOMIZER OPTION

0.1

0.1

0.1

0.1

0.1

0.1

HORIZONTAL DUCT CONNECTIONS

2

0.2

0.3

0.5

0.2

0.3

0.5

1

Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table. (See Note 2 for exception.)

2

Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values on the

respective unit’s blower performance table.

511.06-N3Y

Unitary Products Group

13