Dimensions – ycas0360 (si), Dimensions, Ycas0360 (si) – York MILLENNIUM 28971AR User Manual

Page 66

Advertising
background image

YORK INTERNATIONAL

66

Dimensions –

YCAS0360 (SI)

All dimensions are in mm
unless otherwise noted.

NOTES:

1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,

reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pres-
sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control
panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be
higher than the unit.

2331

651 (EDGE OF
UNIT TO COOLER
CONNECTION)

CONTROL
TRANSFORMER
SERVICE SWITCH

C

543

C

B

B

MICRO-COMPUTER
CONTROL CENTER

OPTIONS PANEL

VIEW A-A

LD03999

CONTROL ENTRY
(12) 22
CONDUIT K.O.'S

229

711

51

120

305

51 TYP.

VIEW B-B

VIEW C-C

191

800

1067

178

CONTROL
OPENING
(229 HIGH)

POWER
OPENING
(533 HIGH)

51

LD04000