Dimensions – ycas0400 - 0440 (si), Dimensions – York MILLENNIUM 28971AR User Manual

Page 70

Advertising
background image

YORK INTERNATIONAL

70

Dimensions –

YCAS0400 - 0440 (SI)

All dimensions are in mm
unless otherwise noted.

NOTES:

1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,

reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pres-
sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control
panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be
higher than the unit.

CONTROL
TRANSFORMER
SERVICE SWITCH

2331

651 (EDGE OF
UNIT TO COOLER
CONNECTION)

C

543

C

OPTIONS PANEL

MICRO-COMPUTER
CONTROL CENTER

B

B

VIEW A-A

LD04007

CONTROL ENTRY
(12) 13
CONDUIT K.O.'S

229

VIEW B-B

51 TYP.

120

305

711

51

VIEW C-C

CONTROL
OPENING
(229 HIGH)

POWER
OPENING
(533 HIGH)

191

800

1067

178

51

LD04008