York MILLENNIUM 28971AR User Manual

Page 95

Advertising
background image

YORK INTERNATIONAL

FORM 201.18-EG1

95

NOTES:

1

.

Field wiring to be in accordance with the current edition of the National Electrical Code as well as all other applicable cod

es and specifications.

2

.

Contacts must be suitable for switching 24VDC, (gold contacts recommended). Wiring shall not be run in the same conduit with

any line voltage wiring.

3

.

T

o

cycle unit on and of

f automatically with contact shown, install a cycling device in series with the flow switch (flsw). Se

e note 2 for contact rating and wiring specifications.

4

.

T

o

stop unit (emergency stop) with contacts other than those shown, install the stop contact between terminals 5 and 1. If a

stop device is not installed, a jumper must be connected between

terminals 5 and 1. Device must have a minimum contact rating of 100

v

a

at 1

15

v

olts a.c.

5

.

Alarm contacts are for annunciating alarm/unit malfunction. Contacts are rated at 1

15V

, 100va, resistive load only

, and must

be suppressed at load by user

.

6

.

See Installation, Operation and Maintenance manual when optional equipment is used.

REFER TO

BOTTOM OF

PAGE 93

FOR LEGEND.