Meter specifications, General – Xantrex Technology XPF 35-10 User Manual

Page 5

Advertising
background image

METER SPECIFICATIONS

Meter Types:

Dual 4 digit meters with 12.5mm (0.5") LEDs. Reading rate 4 Hz.

Meter Resolutions:

10mV, 10mA

Meter Accuracies:

Voltage 0.2% of reading +/-1 digit,
Current 0.5% of reading +/-1 digit

GENERAL

AC Input:

110V-120V AC or 220V-230V AC ± 10%, 50/60Hz.
Installation Category II.

Power Consumption:

600VA max.

Operating Range:

+5ºC to +40ºC, 20% TO 80% RH.

Storage Range:

−40ºC to + 70ºC.

Environmental:

Indoor use at altitudes up to 2000m, Pollution Degree 2.

Safety:

Complies with EN61010-1.

EMC:

Complies with EN61326.

Size:

210 x 130 x 375mm (WxHxD) half rack width x 3U height.

Weight: 5kg

4

Advertising