York YMA024 User Manual

Page 13

Advertising
background image

036-21570-002 Rev. D (0605)

Unitary Products Group

13

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

OUTDOOR UNIT MODEL NO.

YMA03611

INDOOR COIL MODEL NO.

G2FD036S17

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

1000

1200

1400

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

57

62

62

67

72

57

65

T.C.

34.8 38.3 37.7 41.6 40.7 37.8 39.6 39.0 42.0 40.2 40.8 40.9 40.4 42.5 39.8

S.C.

36.0 33.5 28.1 27.7 20.1 38.5 36.5 30.3 29.5 20.6 40.9 39.5 32.6 31.4 21.2

K.W.

2.4 2.4 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

75

T.C.

32.8 35.6 34.7 39.1 39.3 35.5 37.0 35.9 39.7 39.2 38.2 38.4 37.1 40.4 39.1

S.C.

34.0 32.2 26.6 26.7 19.6 36.2 35.0 29.0 28.7 20.4 38.4 37.8 31.4 30.8 21.2

K.W.

2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7

85

T.C.

30.8 32.9 31.7 36.6 38.0 33.3 34.4 32.8 37.5 38.2 35.7 35.9 33.8 38.3 38.3

S.C.

31.9 30.8 25.1 25.7 19.1 33.9 33.4 27.6 28.0 20.1 35.8 36.0 30.1 30.2 21.1

K.W.

2.9 2.9 2.9 2.9 3.0 2.9 2.9 2.9 2.9 3.0 2.9 2.9 2.9 3.0 3.0

95

T.C.

28.9 30.2 28.8 34.2 36.7 31.0 31.9 29.6 35.2 37.1 33.1 33.5 30.4 36.2 37.6

S.C.

29.9 29.5 23.7 24.7 18.7 31.5 31.9 26.3 27.2 19.9 33.2 34.3 28.9 29.7 21.0

K.W.

3.1 3.1 3.1 3.2 3.3 3.1 3.1 3.1 3.2 3.3 3.1 3.2 3.1 3.2 3.3

105

T.C.

27.2 28.2 26.3 31.4 33.5 29.1 29.6 27.1 32.3 33.8 30.9 31.0 27.9 33.2 34.2

S.C.

28.0 27.9 22.6 23.6 17.6 29.4 29.8 24.9 26.0 18.8 31.0 31.8 27.2 28.4 19.9

K.W.

3.3 3.3 3.3 3.4 3.5 3.4 3.4 3.3 3.4 3.5 3.4 3.4 3.4 3.5 3.6

115

T.C.

25.6 26.2 24.0 28.8 30.4 27.2 27.4 24.7 29.5 30.7 28.8 28.6 25.4 30.3 30.9

S.C.

26.2 26.2 21.6 22.6 16.6 27.3 27.8 23.6 24.8 17.7 28.9 29.4 25.6 27.1 18.9

K.W.

3.6 3.6 3.5 3.6 3.8 3.6 3.6 3.6 3.7 3.8 3.7 3.7 3.6 3.7 3.8

125

T.C.

24.0 24.2 21.6 26.1 27.4 25.3 25.2 22.2 26.7 27.5 26.7 26.2 22.8 27.3 27.6

S.C.

24.5 24.6 20.6 21.5 15.6 25.2 25.8 22.3 23.7 16.7 26.8 27.0 24.0 25.8 17.8

K.W.

3.8 3.8 3.8 3.9 4.0 3.9 3.9 3.8 3.9 4.0 3.9 3.9 3.8 3.9 4.1

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

F2RP/F2FP/F3FP036

1.02 0.99 1.00

F2FP/F3FP040

1.02 1.00 1.00

F2RP/F2FP/F3FP042

1.02 1.00 1.00

N1VSB12

G2FD036(S,H)17(T) 1.01 0.99 0.95

N1VSC16

G2FD036(S,H)21(T) 1.03 1.01 0.93

N1AHB08

G2FD036(S,H)17(T) 1.00 1.00 1.00

N1AHB12

G2FD036(S,H)17(T) 1.00 1.00 1.00

N1AHC16

G2FD036(S,H)21(T) 1.03 1.03 1.01

G1FA036S14(T)

0.99 0.99 1.00

G1FA036S17,21(T) 0.98 0.99 0.99

G2FD036(S,H)17(T) 1.00 1.00 1.00

G2FD036(S,H)21(T) 1.01 1.03 0.99

G1NA036S17J

1.00 0.98 1.00

G1NA036S21C

1.00 0.98 1.00

G1HD036

1.01 1.01 1.00

G1HA036H14(T)

1.01 1.00 0.99

G1HA036H17(T)

1.02 1.01 0.99

Variable Speed
Furnace

Coil

T.C.

S.C.

KW

P*DUA12V

G1FA036S14(T)

0.99 0.99 0.97

P*DUB16V

G1FA036S17(T)

0.99 1.00 0.94

P*DUB16V

G2FD036(S,H)17(T) 1.01 1.01 0.95

P*DUC20V

G1FA036S21(T)

1.00 1.00 0.94

P*DUC20V

G2FD036(S,H)21(T) 1.03 1.04 0.93

P1XUB12V

G1FA036S17(T)

0.99 0.99 0.96

P1XUB12V

G2FD036(S,H)17(T) 1.01 1.01 0.97

P1XUC16V

G1FA036S21(T)

0.99 1.00 0.94

P1XUC16V

G2FD036(S,H)21(T) 1.03 1.04 0.94

P1XUC20V

G1FA036S21(T)

0.99 1.00 0.94

P1XUC20V

G2FD036(S,H)21(T) 1.03 1.04 0.93

P1XDB12V

G2FD036(S,H)17(T)

1.01 1.01 0.98

P1XDB12V

G1HA036H17(T)

1.03 1.01 0.99

P1XDC20V

G2FD036(S,H)21(T)

1.03 1.05 0.96

Advertising