THE EFFECT OF ELEVATION ON OIL BURNER

FIRING

The elevation of the installation of a modern high-speed flame retention
oil burner affects the performance of the burner. Allowance for elevation
must be taken into consideration when choosing an oil burner and oper-
ating it above 2000 ft. (610m).

It is especially important in high elevation installations to adjust air set-
tings to match the burner nozzle firing rate. As elevation increases
above sea level, the ambient air contains less oxygen. Because there is
less available oxygen per cubic foot of air, the burner must deliver a
greater volume flow (cfm) of air to provide the proper amount of oxygen
for the amount of oil being burned. This is the reason that an increase in
the burner air setting may be required.

It is also important in high elevation installations to consider the maxi-
mum firing rate of the burner, so that the heat input as required by the
application is maintained. Regardless of elevation, the oil burner has a
maximum volume flow of air that it can deliver. As a result, the maxi-
mum firing rate of the oil burner decreases as the elevation increases,
because the combustion air contains less oxygen. An increase in the
size of a fixed-type retention head, or even the use of an oil burner with
a higher maximum firing rate may be necessary.

The effect of elevation up to 2000 ft. (610 m) is minimal, so no re-rate is
necessary up to 2000 ft. (610 m) elevation. Above 2000 ft. (610 m), for
every 1000 ft. (305 m) above sea level (including the first 2000 ft. (610
m), there is a 1.84% rate reduction of the burner. To assist you, we have
included the following chart and some examples: Refer to Table 7.

ft = feet
m = meters
gph = gallons per hour
l/h = liters per hour

EXAMPLE 1:

.

INSTALLATION AND CHECKING OF OIL PIPING

Location and installation of oil tanks and oil piping must comply with
local codes and regulations. In absence of such codes, follow NFPA 31:
Standard Floor Installation of Oil Burner Equipment.

This equipment must be installed, adjusted, and started only by a
qualified service technician, an individual or agency, licensed and
experienced with all codes and ordinances, who is responsible for
the installation and adjustment of the equipment. The installation
must comply with all local codes and ordinances and with the
National Fire Protection Standard for Liquid Fuel Equipment, NFPA
31 (or in Canada the installation must comply with CSA B139).

This pump must be used with a control system that provides a valve
on delay (pre-purge).

This furnace is designed to operate on #1 FUEL-OIL or #2 FUEL-
OIL ONLY. Do Not burn any other fuel in this furnace. Burning any
fuel except #1 FUEL-OIL or #2 FUEL-OIL in this furnace can cause
premature heat exchanger burnout, high levels of carbon monox-
ide, excessive sooting, a fire hazard, personal injury, property dam-
age, and/or death.
In Canada, the furnace is designed to operate on #1 STOVE OIL or
#2 FURNACE OIL ONLY.

The pressure regulator on the fuel pump must not be adjusted in
excess of 100 PSIG (689 kPa).
Pressures exceeding 100 PSIG (689 kPa) may cause an overheat-
ing condition which can lead to premature heat exchanger failure,
resulting in a fire or explosion, or cause damage to the furnace of
some of its components that will result in property damage and loss
of life. Refer to Figure 16 for Pressure Regulator Location.

TABLE 7: Burner Rating at Elevation Above Sea Level, gph (l/m)

Elevation

(Above Sea Level)

Nozzle Size

0.50

1.892706

0.65

2.460518

ft

m

gph

l/h

gph

l/h

500

152

0.50

1.89

0.65

2.46

1,000

305

0.50

1.89

0.65

2.46

1,500

457

0.50

1.89

0.65

2.46

2,000

610

0.50

1.89

0.65

2.46

2,500

762

0.49

1.86

0.65

2.46

3,000

914

0.48

1.82

0.64

2.42

3,500

1,067

0.48

1.82

0.64

2.42

4,000

1,219

0.47

1.79

0.63

2.37

4,500

1,372

0.47

1.79

0.63

2.37

5,000

1,527

0.46

1.76

0.61

2.33

5,500

1,676

0.46

1.76

0.61

2.33

6,000

1,829

0.46

1.72

0.60

2.28

6,500

1,981

0.46

1.72

0.60

2.28

7,000

2,134

0.45

1.69

0.59

2.24

7,500

2,286

0.45

1.69

0.59

2.24

8,000

2,438

0.44

1.66

0.58

2.20

9,000

2,743

0.43

1.63

0.57

2.16

10,000

3,048

0.42

1.60

0.56

2.12

Note: All examples are for 7000 ft. elevation.
1.84% x 7 (for 7000 ft.) = 12.9%

→ 100% - 12.9% = 87.1%

Re-Rating of the Maximum Firing Rate for Burners @ 7000 ft.

Burner

Model

Maximum Firing

Rate of Burner

@ Sea Level

X

Elevation

Re-rate Factor

@ 7000 ft.

=

Adjusted

Maximum

Firing Rate

AFG

3.00 gph (11.4 L/h) X

87.1%

= 2.61 gph (9.83 Lh)

AF

3.00 gph (11.4 L/h) X

87.1%

= 2.61 gph (9.83 Lh)

FIGURE 16: Oil Pump

4 GPH 100-150 PSI 3450 RPM

3 GPH 150-200 PSI 3450 RPM

NO. 2 & LIGHTER FUEL

INLET

BY-PASS

Exclusively for Beckett

Made by Suntec

INLET

NO. 2 FUEL

A2EA-6520

Beckett

CLEANCUT

USE ONLY WITH

VALVE ON DELAY

Pressure
Adjustment
Screw

Inlet Port
1/4 NPTF

Bleed &
Gauge Port

Return Port
Install 1/16” by Pass Pipe
Plug For Two-Pipe System Only
(Use 5/32” Allen Wrench)

Cordset

By Pass
Solenoid
Valve

Inlet Port

1/4 NPTF
(0.64 cm)

Nozzle Port
3/16 Flare
Fittting