APPLYING FILTER PRESSURE DROP TO

DETERMINE SYSTEM AIRFLOW

Example: For a 84,000 BTUH (38.06 kW) furnace with 1 return open-
ings and operating on high-speed blower, it is found that total system
static is 0.30” w.c. (0.075 kPa). To determine the system airflow, com-
plete the following steps:

Obtain the airflow values at 0.10 w.c. (125 Pa) & 0.20 w.c. (150 Pa)
ESP.

Airflow @ 0.10”: 1175 CFM (60.17 m

3

/min)

Airflow @ 0.20”: 1110 CFM (57.62 m

3

/min)

Subtract the airflow @ 0.10 w.c. (125 Pa) from the airflow @ 0.20 w.c.
(150 Pa) to obtain airflow difference.

1175 - 1110 = -65 CFM (2.55 m

3

/min)

Subtract the total system static from 0.10 w.c. (125 Pa) and divide this
difference by the difference in ESP values in the table, 0.20 w.c.
(150 Pa) - 0.10 w.c. (125 Pa), to obtain a percentage.

(0.30 - 0.10) / (0.20 - 0.10) = 0.5

Multiply percentage by airflow difference to obtain airflow reduction.

(0.5) X (-65) = -32.5

Subtract airflow reduction value to airflow @ 0.10 w.c. (125 Pa) to
obtain actual airflow @ 0.30 wc (144 Pa) ESP.

1050 - 32.5 = 1017.5

FINAL PROCEDURE
Install Furnace Doors

Install the lower door first by sliding the bottom of the door down until
the tabs on the casing base engage the slots in the bottom door end
cap. Then push the top of the lower door in until the door clips snap into
place. Install the upper door in a similar manner, first engaging the slots
in the top of the upper door on the tabs on the casing top. Then snap
the bottom of the upper door into place against the casing.

Finish and Trim

Alcove and Closet Installations may now be finished and trimmed as
necessary.

TABLE 14: Blower Performance CFM

BLOWER PERFORMANCE CFM - DFAA066

FACTORY EQUIPPED WITH STANDARD BLOWERS AND FILTERS

EXTERNAL STATIC PRESSURE, INCHES WC (kPa)

Blower Speed

BTU/H (kW)

Input / Output

CFM

(m

3

/ min)

0.1 (0.025)

0.2 (0.050)

0.3 (0.075)

0.4 (0.099)

0.5 (0.124)

cfm

cm/m

cfm

cm/m

cfm

cm/m

cfm

cm/m

cfm

cm/m

Single Speed - No Coil

66(19.34) / 53(15.55) 1050(29.73)

1175

33.3

1110

31.4

1050

29.7

1000

28.3

950

26.9

Single Speed - With Dry Coil 66(19.34) / 53(15.55) 1050(29.73)

1125

31.9

1070

30.3

1020

28.9

960

27.2

910

25.8

BLOWER PERFORMANCE CFM - DFAA084

EXTERNAL STATIC PRESSURE, INCHES WC (kPa)

Blower Speed

BTU/H (kW)

Input / Output

CFM

(m

3

/ min)

0.1 (0.025)

0.2 (0.050)

0.3 (0.075)

0.4 (0.099)

0.5 (0.124)

cfm

cm/m

cfm

cm/m

cfm

cm/m

cfm

cm/m

cfm

cm/m

Single Speed - No Coil

84(24.62) / 67(19.63) 1250(35.39)

1370

38.8

1305

37.0

1245

35.3

1175

33.3

1100

31.1

Single Speed - With Dry Coil 84(24.62) / 67(19.63) 1250(35.39)

1265

35.8

1195

33.8

1120

31.7

1045

29.6

1015

28.7

BLOWER PERFORMANCE CFM - DFAH066

EXTERNAL STATIC PRESSURE, INCHES WC (kPa)

Blower Speed

BTU/H (kW)

Input / Output

CFM

(m

3

/ min)

0.1 (0.025)

0.2 (0.050)

0.3 (0.075)

0.4 (0.099)

0.5 (0.124)

cfm

cm/m

cfm

cm/m

cfm

cm/m

cfm

cm/m

cfm

cm/m

Single Speed - No Coil

66(19.34) / 53(15.55 1050(29.73)

1155

32.7

1111

31.5

1055

29.9

995

28.2

920

26.1

BLOWER PERFORMANCE CFM - DFAH084

EXTERNAL STATIC PRESSURE, INCHES WC (kPa)

Blower Speed

BTU/H (kW)

Input / Output

CFM

(m

3

/ min)

0.1 (0.025)

0.2 (0.050)

0.3 (0.075)

0.4 (0.099)

0.5 (0.124)

cfm

cm/m

cfm

cm/m

cfm

cm/m

cfm

cm/m

cfm

cm/m

Single Speed - No Coil

84(24.62) / 67(19.63) 1250(35.39)

1127

31.9

1062

30.1

1005

28.5

952

27.0

887

25.1

NOTES: