Figure 3: air distribution systems, Figure 4: closet to door clearance - 5” or greater – York DFAH User Manual

Page 7

Advertising
background image

107272-UIM-B-1105

Unitary Products Group

7

FIGURE 3: Air Distribution Systems

A

Single trunk duct

Dual trunk duct

Transition duct

1

B*

Dual trunk duct with crossover connector

Crossover

C

Transition Duct with Branches

Branches

3

1. Crossover Duct must be centered directly under furnace.
2. Use 12” (30.5 cm) Diameter Round or insulated Flex-duct only.
3. Terminate Flex-duct (opposite furnace) in the center of the trunk duct.
4. Flex-duct material must be pulled tight — No Loops or unnecessary dips — Air Flow may be impeded.

4

2

FIGURE 4: Closet To Door Clearance - 5” or Greater

5 in (12.7 cm) or greater * Closet
to Door Clearance

Furnace to Closet Door Clearance —
5 Inches (12.7 cm) or more

1.

2.

Return Air Grille Part No.
7900-287P/A * White

The closet door

have a minimum of

of free area in the upper half of the door.

MUST

250 Inches (1613 cm )

2

2

250 IN. (161 cm )
MINIMUM
FREE AREA

2

2

50 IN. (322 cm )
MINIMUM
FREE AREA

2

2

250 IN. (161 cm )
MINIMUM
FREE AREA

2

2

B

CLOSET

DOOR

FURNACE

A

If opening for return air is located in the floor or sidewalls and
below the top of the furnace casing:

Return Air Closet Door Part No.
7900-7771/C* White

6 inches (15.2 cm) minimum clearance must be maintained from
the front of furnace.

6 inches (15.2 cm) minimum clearance must be provided on side
where return is located, and

FIGURE 5: Furnace To Closet Door Clearance - 1” To 5”

Furnace to Closet Door Clearance —
Greater than 1 Inch (2.54 cm) and Up to 5 (12.7 cm) Inches

1.

2. A fully louvered closet door

have a minimum of

of free area in the upper half of the door.

MUST

250 Inches

2

2

(1613 cm )

The closet door

have a minimum of

(1613 cm

f free

area in the upper half of the door and a minimum of

(322 cm ) of

free area in the lower area of the door.

MUST

250 Inches

50 Inches

The lower closet door grille may be

omitted if an undercut of 2-1/2 inches (16.1 cm) is provided in the door.

2

2

2

2

) o

250 IN. (161 cm )
MINIMUM
FREE AREA

2

2

50 IN. (322 cm )
MINIMUM
FREE AREA

2

2

250 IN. (161cm )
MINIMUM
FREE AREA

2

2

B

As an option to the lower grill,
an undercut of 2-1/2" will provide

50 inches (322 cm ) of free area.

2

2

FIGURE 6: Furnace To Closet Door Clearance - Less Than 1”

Furnace to Closet Door Clearance —
Less than 1 Inch (2.54 cm)

The closet door MUST have three return air grilles. The total free area of the
two upper grilles must be minimum of

(1613 cm ) . The total

free area of the lower grille MUST be a minimum of

.

250 Inches

50 Inches (322 cm )

2

2

2

2

The grilles MUST BE ALIGNED directly opposite the return air grille of
the furnace door.

250 IN. (161 cm )
MINIMUM
FREE AREA

2

2

50 IN. (322 cm )
MINIMUM
FREE AREA

2

2