Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO.
YHJD
48S41S1
INDOOR COIL MODEL NO.
AHP/SHP48
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1400
1600
1800
ID
DB
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID
WB
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
46.3 49.0 49.0 53.3 57.3 48.3 49.9 49.7 54.0 58.4 50.2 50.8 50.4 54.8 59.4
S.C.
46.3 43.0 36.2 35.8 29.6 48.3 45.5 37.9 37.6 30.7 50.2 48.0 39.6 39.4 31.8
KW
2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
75
T.C.
44.6 46.6 46.6 50.7 54.8 46.3 47.5 47.3 51.6 55.7 47.9 48.4 48.0 52.4 56.7
S.C.
44.6 41.9 35.2 34.8 28.3 46.3 44.4 37.0 36.6 29.4 47.9 46.9 38.8 38.4 30.5
KW
2.9 2.8 2.8 2.9 2.9 2.9 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9
85
T.C.
42.9 44.1 44.2 48.2 52.2 44.3 45.0 44.9 49.1 53.1 45.7 45.9 45.7 50.0 54.0
S.C.
42.9 40.9 34.3 33.8 27.1 44.3 43.3 36.1 35.7 28.1 45.7 45.7 38.0 37.5 29.1
KW
3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2
95
T.C.
41.1 41.7 41.7 45.7 49.7 42.3 42.6 42.5 46.6 50.5 43.4 43.5 43.3 47.5 51.3
S.C.
41.1 39.8 33.3 32.8 25.8 42.3 42.2 35.2 34.7 26.8 43.4 43.5 37.2 36.6 27.8
KW
3.5 3.5 3.5 3.6 3.6 3.5 3.5 3.5 3.6 3.6 3.5 3.5 3.5 3.6 3.6
105
T.C.
38.8 38.7 38.7 42.4 46.4 39.8 39.8 39.4 43.2 47.0 40.9 40.8 40.0 43.9 47.6
S.C.
38.8 37.7 32.0 31.6 24.6 39.8 39.7 33.9 33.5 25.6 40.9 40.8 35.9 35.3 26.6
KW
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0
115
T.C.
36.4 35.9 35.9 39.3 43.3 37.5 37.0 36.3 39.8 43.7 38.5 38.1 36.8 40.4 44.1
S.C.
36.4 35.7 30.7 30.4 23.4 37.5 37.0 32.7 32.2 24.3 38.5 38.1 34.6 34.1 25.3
KW
4.4 4.4 4.4 4.4 4.5 4.4 4.4 4.4 4.4 4.5 4.4 4.4 4.4 4.4 4.5
125
T.C.
34.1 33.0 33.0 36.1 40.1 35.1 34.2 33.3 36.5 40.4 36.0 35.4 33.6 36.9 40.6
S.C.
34.1 33.0 29.5 29.2 22.1 35.1 34.2 31.4 31.0 23.1 36.0 35.4 33.3 32.9 24.1
KW
4.8 4.8 4.8 4.8 4.9 4.8 4.8 4.8 4.9 4.9 4.8 4.8 4.8 4.9 4.9
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC48
1.00 1.01 1.00
–
FC/MC/PC60
1.00 1.02 1.00
–
HC60
1.00 1.02 1.00
–
HD60
1.00 1.01 1.00
–
MC62
1.01 1.02 1.00
AHP60
–
1.01 1.03 1.00
AHX48
–
1.04
1.08
0.98
AV/SV*48
–
1.02 1.03 1.00
AV/SV*60
–
1.03
1.03
0.96
F4FV060
–
1.02 1.03 1.00
F5FP048
–
1.02 1.05 1.00
F5FP060
–
1.02 1.05 1.00
F6FP048
–
1.05
1.07
0.98
MA16C
FC/MC/PC48C
1.00 1.01 1.00
MA20D
FC/MC/PC48D
1.00 1.01 1.00
MV16C
FC/MC/PC48C
1.02 1.02 1.00
MV20D
FC/MC/PC48D
1.01 1.02 1.00
MA16C
FC/MC/PC60C
1.00 1.02 1.00
MA20D
FC/MC/PC60D
1.00 1.02 1.00
MV20D
FC/MC/PC60D
1.01 1.03 1.00
MA20D
MC62D
1.01 1.02 1.00
MV20D
MC62D
1.02 1.03 1.00
Furnaces
Coils
T.C.
S.C.
KW
T*(8,L)X*C16
FC/PC60C
1.03
1.04
0.98
T*9X*C16
FC/PC60C
1.03
1.04
0.99
T*(8,L)X*C20
FC/MC/PC60D
1.03
1.04
0.98
T*9X*C20
FC/PC60C
1.03
1.04
0.98
T*9X*D20
FC/MC/PC60D
1.02
1.02
0.94
T*9X*D20
FC/MC62D
1.03
1.06
0.99
T*(8,L)X*C16
UC60C
1.02
1.04
0.98
T*(8,L)X*C20
UC60D
1.02
1.03
0.94
T*9X*C16
UC60C
1.02
1.04
0.99
T*9X*C20
UC60C
1.03
1.04
0.98
T*9X*D20
UC60D
1.02
1.01
0.94
(
Y
*9C/T*9V)*D20 FC/MC/PC60D
1.00 1.02 0.98
(
Y
*9C/T*9V)*D20 FC/MC62D
1.00 1.03 0.98
Y
*(8,L)C*C16
FC/PC60C
1.00 1.03 0.98
Y
*(8,L)C*C20
FC/PC60C
1.01 1.03 0.96
(
Y
*9C/T*9V)*C16 FC/PC60C
1.00 1.02 0.99
(
Y
*9C/T*9V)*C20 FC/PC60C
1.00 1.02 0.99
(
Y
*9C/T*9V)*D20 HC60
0.99 1.02 0.98
Y
*(8,L)C*C16
HD60
1.00 1.03 0.98
Y
*(8,L)C*C20
HD60
1.01 1.03 0.96
(
Y
*9C/T*9V)*C16 HD60
1.00 1.03 0.99
(
Y
*9C/T*9V)*C20 HD60
1.00 1.03 0.99
(
Y
*9C/T*9V)*D20 HD60
1.00 1.03 0.98
Y
*(8,L)C*C16
UC60C
0.99 1.00 0.98
Y
*(8,L)C*C20
UC60C
0.99 1.01 0.96
(
Y
*9C/T*9V)*C16 UC60C
0.98 1.00 0.99
(
Y
*9C/T*9V)*C20 UC60C
0.98 1.00 0.99
(
Y
*9C/T*9V)*D20 UC60D
0.99 1.00 0.98
Furnaces
Coils
T.C.
S.C.
KW