York YHJD18 User Manual

Page 27

Advertising
background image

Johnson Controls Unitary Products

27

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

CONDENSING UNIT MODEL NO.

YHJD

60S41S1

INDOOR COIL MODEL NO.

FC/MC62

CONDENSING

ENTERING AIR

TEMPERATURE

IDCFM

1600

1800

2000

ID

DB

(°F)

80 80

75

80

80

80 80 75

80

80 80 80

75 80 80

ID

WB

(°F)

57 62 62 67 72 57 62 62 67 72 57 62 62 67 72

65

T.C.

54.0 57.1 56.9 62.3 67.6 56.0 57.9 57.8 63.4 69.1 58.0 58.7 58.7 64.4 70.5

S.C.

54.0 51.0 43.4 42.9 34.8 56.0 54.4 45.4 45.0 36.2 58.0 57.7 47.4 47.1 37.6

KW

2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9 2.8 2.8 2.8 2.9 2.9

75

T.C.

51.9 54.1 53.9 59.2 64.5 53.7 54.9 54.8 60.2 65.7 55.5 55.7 55.6 61.2 66.9

S.C.

51.9 49.8 42.0 41.7 33.5 53.7 52.7 44.1 43.8 34.8 55.5 55.6 46.1 45.8 36.2

KW

3.2 3.2 3.2 3.3 3.3 3.2 3.2 3.2 3.3 3.3 3.2 3.2 3.2 3.3 3.3

85

T.C.

49.7 51.1 51.0 56.2 61.4 51.3 51.9 51.8 57.1 62.4 53.0 52.7 52.6 58.0 63.4

S.C.

49.7 48.6 40.7 40.5 32.2 51.3 51.1 42.8 42.5 33.4 53.0 52.7 44.9 44.6 34.7

KW

3.6 3.6 3.6 3.6 3.7 3.6 3.6 3.6 3.7 3.7 3.6 3.6 3.6 3.7 3.7

95

T.C.

47.6 48.1 48.1 53.1 58.3 49.0 48.9 48.8 54.0 59.0 50.4 49.7 49.5 54.8 59.8

S.C.

47.6 47.4 39.3 39.2 30.9 49.0 48.9 41.5 41.3 32.0 50.4 49.7 43.6 43.3 33.2

KW

4.0 4.0 4.0 4.0 4.1 4.0 4.0 4.0 4.1 4.1 4.0 4.0 4.0 4.1 4.1

105

T.C.

44.3 44.6 44.1 48.7 53.5 45.6 45.5 44.6 49.3 54.1 46.8 46.3 45.2 50.0 54.7

S.C.

44.3 44.6 37.6 37.4 29.0 45.6 45.5 39.7 39.4 30.2 46.8 46.3 41.8 41.5 31.3

KW

4.5 4.5 4.5 4.5 4.6 4.5 4.5 4.5 4.5 4.6 4.5 4.5 4.5 4.5 4.6

115

T.C.

41.1 41.3 40.2 44.4 48.9 42.2 42.2 40.6 44.9 49.4 43.3 43.1 41.0 45.3 49.9

S.C.

41.1 41.3 35.9 35.7 27.3 42.2 42.2 37.9 37.7 28.4 43.3 43.1 40.0 39.7 29.5

KW

4.9 5.0 4.9 5.0 5.0 5.0 5.0 4.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0

125

T.C.

37.9 37.9 36.2 40.1 44.3 38.8 38.8 36.5 40.4 44.6 39.8 39.8 36.8 40.7 45.0

S.C.

37.9 37.9 34.2 33.9 25.5 38.8 38.8 36.2 35.9 26.6 39.8 39.8 36.8 37.9 27.7

KW

5.4 5.4 5.4 5.4 5.5 5.4 5.4 5.4 5.4 5.5 5.4 5.4 5.4 5.4 5.5

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Air Handlers

Coils

T.C.

S.C.

KW

AHX60

1.06

1.13

1.05

F6FP060

1.06

1.09

1.01

MA20D MC62D

1.00

1.00

1.00

MV20D MC62D

1.01

1.01

1.00

Furnaces

Coils

T.C.

S.C.

KW

T*(8,L)X*C20

FC/MC62D

1.05

1.08

0.99

T*9X*D20

FC/MC62D

1.02

1.02

1.02

(

Y

*9C/T*9V)*D20 FC/MC/PC60D

0.99 0.96 0.97

Y

*(8,L)C*C20

FC/MC62D

1.00 0.97 0.96

(

Y

*9C/T*9V)*C20 FC/MC62D

0.99 0.96 0.98

Advertising