Johnson Controls Unitary Products

Multipliers for determining the performance with other indoor sections.

Continued on next page.

HEATING PERFORMANCE DATA

CONDENSING UNIT MODEL NO

YHJD

42S41S1

EVAPORATOR COIL MODEL NO

FC/MC/PC/UC48

AIR TEMP.

ENTERING

OUTDOOR UNIT

AIR TEMP.

ENTERING

INDOOR COIL

ID CFM

1200

1400

1600

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

60

60

48.7 3.5 4.1 48.7 3.5 4.1 48.7 3.4 4.2

70

47.8 3.8 3.6 48.6 3.8 3.7 49.5 3.8 3.8

80

46.8 4.2 3.3 48.6 4.2 3.4 50.3 4.1 3.6

47

60

42.5 3.3 3.8 42.9 3.3 3.8 43.3 3.2 3.9

70

42.3 3.6 3.4 42.7 3.6 3.5 43.1 3.6 3.6

80

42.0 3.9 3.1 42.4 3.9 3.2 42.9 3.9 3.3

40

60

40.1 3.2 3.7 40.5 3.2 3.7 40.8 3.2 3.8

70

39.1 3.5 3.3 39.6 3.5 3.3 40.0 3.5 3.4

80

38.2 3.8 2.9 38.7 3.8 3.0 39.2 3.8 3.0

30

60

33.5 3.8 2.6 33.8 3.7 2.7 34.1 3.7 2.7

70

34.8 3.4 3.0 34.5 3.4 3.0 34.1 3.4 2.9

80

36.2 3.1 3.4 35.1 3.1 3.3 34.1 3.1 3.2

17

60

27.8 3.6 2.2 28.4 3.6 2.3 29.1 3.6 2.4

70

28.3 3.3 2.5 28.8 3.3 2.5 29.2 3.3 2.6

80

28.8 3.0 2.8 29.1 3.0 2.8 29.4 3.0 2.8

10

60

26.3 3.6 2.1 26.9 3.6 2.2 27.6 3.6 2.2

70

25.6 3.3 2.3 26.8 3.3 2.4 28.0 3.3 2.5

80

24.8 3.0 2.4 26.6 3.0 2.6 28.4 3.0 2.8

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handlers

Coils

MBH

KW

COP

FC/MC/PC60

1.00 1.06 0.94

HC42

0.99 0.99 1.00

HC60

1.00 1.06 0.94

HD60 0.99

0.89

1.11

AHP/SHP48

1.00

1.00

1.00

AHX42

0.98

1.05

0.93

AHX48

0.98

1.07

0.92

AV/SV*48

0.98

1.05

0.94

F4FP045

1.01 1.07 0.94

F5FP048

0.99 1.01 0.98

F6FP042

0.99

1.06

0.94

F6FP048

0.99

1.09

0.91

MA14D

FC/MC/PC48D

1.00 1.00 1.00

MA16C

FC/MC/PC48C

1.00 1.00 1.00

MV16C

FC/MC/PC48C

0.99 0.99 1.00

MV20D

FC/MC/PC48D

0.98 0.98 1.00

MA14D

FC/MC/PC60D

1.00 1.06 0.94

MA16C

FC/MC/PC60C

1.00 1.06 0.94

MV20D

FC/MC/PC60D

0.98 1.04 0.94