Printers, Fig. 48 – continued, Fig. 49 – sample printout (security log) – York R123 User Manual

Page 122: York setpoint change log chiller id 163

Advertising
background image

YORK INTERNATIONAL

122

FORM 160.55-O1 (604)

FIG. 48 – CONTINUED

Printers

YORK SETPOINT CHANGE LOG

CHILLER ID 163

© 1997 – 2000 YORK INTERNATIONAL COR

PO

RA

TION

Mon 09 Oct 2000 3:33:47 PM

Log Entry 1 Evaporator - Leaving Chilled Local Setpoint

---------------------------------------------------------------------------

Date = 05 Oct 2001

Time = 4:23:49 PM

Access Level = Service

User Id = 4268

Old Value = 46.5 ~F

New Value = 48.0 ~F

Log Entry 2 Condenser - High Pressure Warning Threshold

---------------------------------------------------------------------------

Date = 05 Oct 2001

Time = 1:36:12 PM

Access Level = Service

User Id = 4268

Old Value = 162.5 Psig

New Value = 225.0 Psig

Log Entry 3 Condenser - Drop Leg

---------------------------------------------------------------------------

Date = 05 Oct 2001

Time = 1:36:02 PM

Access Level = Service

User Id = 4268

Old Value = Disabled

New Value = Enabled

Log Entry 4 Evaporator - Refrigerant

---------------------------------------------------------------------------

Date = 05 Oct 2001

Time = 1:35:48 PM

Access Level = Service

User Id = 4268

Old Value = Disabled

New Value = Enabled

FIG. 49 – SAMPLE PRINTOUT (SECURITY LOG)

[Skip the following section if Motor Type is not VSD]

Variable Speed Drive

--------------------------------------------------------------------------

Motor Run = Off

% Full Load Amps = 0 %

Pre-Rotation Vanes Position = 0 %

Full Load Amps = 402 A

Precharge Relay Output = Off

Trigger SCR Output = Off

Water Pump Output = Off

KW Hours = 14528 KWH

Input Power = 150 KW

Output Frequency = 0 Hz

Output Voltage = 800 V

DC Bus Voltage = 600 V

DC Inverter Link Current = 300 A

Phase A Output Current = 0 A

Phase B Output Current = 0 A

Phase C Output Current = 0 A

Internal Ambient Temperature = 88 ~F

Converter Heatsink Temperature = 102 ~F

Phase A Heatsink Temperature = 93 ~F

Phase B Heatsink Temperature = 99 ~F

Phase C Heatsink Temperature = 97 ~F

[Skip the following section if Motor Type is not VSD,

or Filter is not

present]

Harmonic Filter Data

--------------------------------------------------------------------------

Precharge Contactor = Off

Supply Contactor = Off

Operating Mode = Stopped

Phase Rotation = ABC

Total Supply KVA = 148 KVA

Total Power Factor = 0.97

DC Bus Voltage = 608 V

Heatsink Temperature = 102 ~F

Voltage Peak N-L1 = 200 V

Voltage Peak N-L2 = 200 V

Voltage Peak N-L3 = 200 V

L1-L2 RMS Voltage = 215 V

L2-L3 RMS Voltage = 215 V

L3-L1 RMS Voltage = 215 V

L1 RMS Filter Current = 150 A

L2 RMS Filter Current = 150 A

L3 RMS Filter Current = 150 A

L1 RMS Supply Current = 152 A

L2 RMS Supply Current = 152 A

L3 RMS Supply Current = 152 A

L1 Voltage Total Harmonic Distortion = 1.5 %

L2 Voltage Total Harmonic Distortion = 1.2 %

L3 Voltage Total Harmonic Distortion = 1.1 %

L1 Supply Current Total Demand Distortion = 2.6 %

L2 Supply Current Total Demand Distortion = 2.3 %