Oil sump screen – York R123 User Manual

Page 40

Advertising
background image

YORK INTERNATIONAL

40

FORM 160.55-O1 (604)

OIL SUMP SCREEN

OVERVIEW

This screen displays a close-up of the chiller oil
sump.

DISPLAY ONLY

Oil Sump Temperature
Displays the temperature of the oil in the sump.

Oil Pressure
Displays the pressure differential between the high side
oil pressure transducer (output of oil Þ lter) and the low
side oil pressure transducer (compressor housing). If
either of the transducers used to calculate this dif fer -
en tial is out of range, the display Þ eld will show XX.X.

Oil Pump Run Output (LED)
Indicates whether the Oil Pump is being commanded
to operate.

Manual Oil Pump Operation Time Left
Displays the time remaining in the 10-minute manual
oil pump operation described below.

PROGRAMMABLE

Manual Pump

Access Level Required: OPERATOR

This key puts the Oil Pump control in Manual Mode and
forces it to RUN. The Oil Pump is limited to run ning for
a maximum of ten (10) minutes. If a longer running time
is desired, this key must be pressed again. Manual Oil
Pump control is disabled (and the button hidden) during
system prelube, system run and system coastdown.

NAVIGATION

Home

Access Level Required: VIEW
Causes an instant return to the Home Screen.

00356VIP

FIG. 15

OptiView Control Center

Advertising
This manual is related to the following products:

YT