System op er at ing pro ce dures – York R123 User Manual

Page 126

Advertising
background image

YORK INTERNATIONAL

126

FORM 160.55-O1 (604)

"SYSTEM SHUTDOWN"

DISPLAY

MESSAGE

"SYSTEM RUN"

"SYSTEM PRELUBE"

(OIL PUMP PRE-RUN)

"SYSTEM COASTDOWN"

(OIL PUMP POST-RUN)

0

25

30

330

1800

(0.4)

(0.5)

(5.5)

(30)

START

RESTART (IF

FIVE SUCCESSIVE

RESTARTS HAVE

NOT OCCURRED)

RESTART (ONLY
AFTER THE FIFTH
SUCCESSIVE RESTART)

TIME IN SECONDS (MINUTES)

ENERGIZE

(OPEN)

VENT

SOLENOID

CHECK

OIL PRESS.

150 SEC.

(2.5 MIN.)

"SYSTEM SHUTDOWN"

DISPLAY

MESSAGE

"SYSTEM RUN"

"SYSTEM PRELUBE"

(OIL PUMP PRE-RUN)

"SYSTEM COASTDOWN"

(OIL PUMP POST-RUN)

0

25

30

330

1800

(0.4)

(0.5)

(5.5)

(30)

START

TIME IN SECONDS (MINUTES)

ENERGIZE

(OPEN)

VENT LINE
SOLENOID

CHECK

OIL PRESS.

150 SEC.

(2.5 MIN.)

RESTART

FIG. 54 – OPERATION SEQUENCE TIMING DIAGRAM
(ELECTRO-MECHANICAL AND SOLID STATE STARTER APPLICATIONS)

LD04643

System Op er at ing Pro ce dures

FIG. 55 – OPERATION SEQUENCE TIMING DIAGRAM
(COMPRESSOR MOTOR VARIABLE SPEED DRIVE APPLICATIONS)

LD04644

Advertising
This manual is related to the following products:

YT