Table 30: physical data, Table 31: electric heat correction factors, Table 32: voltage limitations – York DJ 048 User Manual

Page 28: 30 physical data, 31 electric heat correction factors, 32 voltage limitations

Advertising
background image

254596-YTG-A-0306

28

Unitary Products Group

TABLE 30: PHYSICAL DATA

MODELS

DJ

036

048

060

EVAPORATOR

BLOWER

Centrifugal Blower (Dia. x Wd. in.)

12 X 10

12 X 10

12 X 10

Fan Motor HP (Belt Drive)

1-1/2

1-1/2

1-1/2

EVAPORATOR

COIL

Rows Deep

3

4

4

Fins Per Inch

13

13

13

Face Area (Sq. Ft.)

5.1

5.1

5.1

CONDENSER

FANS

Propeller Dia. (in.)

24

24

24

Fan Motor Hp

1/2

1/2

1/2

Nom. CFM

4200

4200

4200

CONDENSER

COILS

Rows Deep

2

2

2

Fins Per Inch

18

18

18

Face Area (Sq. Ft.)

17.1

17.1

17.1

COMPRESSOR

(Qty. Per Unit)

Quantity

1

1

1

Type

Recip.

Recip.

Scroll

AIR

FILTERS

Quantity Per Unit (15” X 20” X 1” or 2“)

2

2

2

Quantity Per Unit (14” X 25” X 1” or 2“)

1

1

1

Total Face Area (sq. ft.)

6.3

6.3

6.3

CHARGE

Refrigerant 22 (lbs./oz.)

9/4

9/8

11/0

TABLE 31: ELECTRIC HEAT CORRECTION

FACTORS

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTI-

PLIER

208

208

1.00

240

230

0.92

480

460

0.92

600

575

0.92

TABLE 32: VOLTAGE LIMITATIONS

1

1. Utilization Range “A” in accordance with ARI Standard

110.

POWER SUPPLY

VOLTAGE

MIN.

MAX.

208/230-1-60

187

252

208/230-3-60

187

252

460-3-60

432

504

575-3-60

540

630

Advertising