Typical power wiring typical control wiring, Figure 2 - typical field power & control wiring, Cooling only (24 volt thermostat) – York DJ 048 User Manual

Page 29: Cooling / heating (24 volt thermostat)

Advertising
background image

254596-YTG-A-0306

Unitary Products Group

29

FIGURE 2 -

TYPICAL FIELD POWER & CONTROL WIRING

REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTEC-
TION AND WIRING.

RC

RH

Y1

Y2

W1

W2

G

LED 1

LED 2

COM

A1

A2

T

T

B

R

Y1

Y2

G

C

X

OCC

W2

W1

THERMOSTAT

1

TERMINALS

UNIT TERMINAL

STRIP TB1

24 VOLT

TRANSFORMER

TO REMOTE SENSOR

2TH040702224 IF USED

NOT
USED

ADD

JUMPER

ADD

JUMPER

4

4

3

2

1

ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).

2

SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.

3

SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE

ELECTRIC HEATER OR 2 STAGE GAS HEAT.

4

REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.

COOLING / HEATING (ELECTRONIC THERMOSTAT)

MULTI STAGE

RH

RC

Y

W

G

R

Y1

W1

C

G

ADD

JUMPER

THERMOSTAT

1

TERMINALS

UNIT TERMINAL

STRIP TB1

24 VOLT

TRANSFORMER

1

ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.

COOLING / HEATING (ELECTRONIC THERMOSTAT)

SINGLE STAGE

RV

YC

GF

R

Y1

C

Y2

THERMOSTAT

1

TERMINALS

UNIT TERMINAL

STRIP TB1

24 VOLT

TRANSFORMER

1

24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.

G

COOLING ONLY (24 VOLT THERMOSTAT)

RC

Y

R

Y1

Y2

W1

W

W2

G

C

G

RH

THERMOSTAT

TERMINALS

UNIT TERMINAL

STRIP TB1

24 VOLT

TRANSFORMER

ADD

JUMPER

1

24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.

1

COOLING / HEATING (24 VOLT THERMOSTAT)

TYPICAL POWER WIRING

TYPICAL CONTROL WIRING

Advertising