254596-YTG-A-0306

32

Unitary Products Group

FIGURE 7 -

UNIT DIMENSIONS (REAR VIEW)

FIGURE 8 -

DISCONNECT/BLOWER ACCESS
LOCATION

TABLE 33: UTILITIES ENTRY

HOLE

OPENING SIZE (DIA.)

USED FOR

A

7/8” KO

1

1. Opening in the bottom to the unit can be located by the

side in the insulation.

Control Wiring

2

2. Do not remove the 2” knockout ring.

Side

Bottom

B

2” KO1

Power Wiring

Side

Bottom

C

1-5/8” KO

Gas Piping (Front)

D

1-1/2” KO

Gas Piping (Bottom)

DISCONNECT SWITCH LOCATION

AND MOTOR ACCESS PANEL FOR

UNIT WITH “BELT-DRIVE” OPTION

CONTROL BOX

ACCESS

A,B

WIRING ENTRY

(See Detail “B”)

MOUNTING BRACKET

FOR DICONNECT SWITCH

(Shipped attached to the

blower housing inside

the blower compartment)

FIELD-SUPPLIED

DISCONNECT SWITCH

LOCATION

BLOWER MOTOR

ACCESS

FILTER

ACCESS

DOT PLUGS

TABLE 34: MINIMUM CLEARANCES

LOCATION

CLEARANCE

Front

24” (Cooling/Electric Heat)

32” (Gas Heat)

Rear

12” (Less Economizer)

36” (With Economizer or Fixed

Air/Motorized Damper)

Left Side (Filter Access)

24” (Less Economizer)

36” (With Economizer)

Right Side (Cond. Coil)

24”

Below Unit

1

1. Units may be installed on combustible floors made

from wood or class A, B, or C roof covering material.

0”

Above Unit

2

2. Units must be installed outdoors. Overhanging struc-

tures or shrubs should not obstruct condenser air dis-
charge outlet.

72” (For

Condenser Air Discharge)