York DJ 048 User Manual

Page 8

Advertising
background image

254596-YTG-A-0306

8

Unitary Products Group

TABLE 4: DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)

UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP

63

80

82

80

82

78

83

81

85

125

76

77

76

77

82

83

81

82

250

56

59

56

60

60

61

58

60

500

50

50

49

50

54

54

51

52

1000

40

43

39

42

49

50

44

45

2000

41

42

40

42

49

49

43

44

4000

41

41

41 41

49 49 41 41

8000

45

45

45

45

47

47

45

45

DJ036 / 3 Ton / Belt Drive

Horizontal Ducted Inlet

630

631

879

885

0.2

0.3

0.2

0.7

1116

928

1979

1020

0.41

0.37

0.76

0.53

Octave Center Freq.

ID Blower

Only (dB)

Cooling

Operation

2

(dB)

ID Blower

Only (dB)

4. Test duct termination is flush with reverberation room wall.

5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

Cooling

Operation

2

(dB)

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2. Cooling Operation – ID blower, compressor and outdoor fan operating.

3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

Cooling

Operation

2

(dB)

ID Blower

Only (dB)

Cooling

Operation

2

(dB)

ID Blower

Only (dB)

TABLE 5: DJ036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL
CONFIGURATION
Indoor Blower Speed (RPM)
Blower Static Pressure (IWG)
Airflow (CFM)
Blower Motor BHP

63

80

84

80

83

85

87

84

87

125

74

77

74

76

80

82

80

83

250

58

61

58

61

68

68

63

65

500

48

51

47

50

58

58

53

54

1000

41

45

39

43

55

55

49

50

2000

39

41

37

39

53

53

46

47

4000

41

41

38

38

55

55

49

49

8000

45

45

44

44

52

53

47

47

4. Test duct termination is flush with reverberation room wall.

5. Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

Cooling

Operation

2

(dB)

1. Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2. Cooling Operation – ID blower, compressor and outdoor fan operating.

3. Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

Cooling

Operation

2

(dB)

ID Blower

Only (dB)

Cooling

Operation

2

(dB)

ID Blower

Only (dB)

Octave Center Freq.

ID Blower

Only (dB)

Cooling

Operation

2

(dB)

ID Blower

Only (dB)

0.41

0.37

0.76

0.53

1116

928

1979

1020

0.2

0.3

0.2

0.7

DJ036 / 3 Ton / Belt Drive

Horizontal Ducted Discharge

630

631

879

885

Advertising