Chapter 2 System Description

2-4

rectifier failure, rectifier self-protection, the red LED is on. Once the

alarm is gone, the red LED goes off.

The controller of the PSE2500-A3 has two major functions:

I. Monitoring the system operation status

Inside PSE2500-A3 there is an AC sensor card, which can

sample the AC input voltage. The sampled signal is sent into the

controller for data processing. Once the input voltage is lower than the

pre-set alarm level of the input low voltage, the controller reports an

AC input under-voltage alarm. Likewise, if the input voltage is higher

than the pre-set alarm level of the input high voltage, the controller

reports an AC input over-voltage alarm.

The sampled DC output voltage signal is also sent into the

controller. Once the output voltage is lower than the pre-set alarm

level of the output low voltage, the controller will reports a DC Low

alarm. Likewise, if the output voltage is higher than the pre-set alarm

level of the output high voltage, the controller reports a DC output high

alarm.

The rectifier communicates with the controller through RS485

bus. The working status of the rectifier is passed to the controller in

this way. Once the rectifier has an alarm, the information is passed to

the controller. The rectifier failure alarm includes: AC input failure, DC

output failure, fan failure, output high, over temperature, and module

shut-down.

II. Communicate with deamon systems

The controller supports China national standard protocol YD/T

1104-2001. User can apply this protocol to read system information or