3Com External PoE Power System PSE2500-A3 User Manual

Page 31

Advertising
background image

User Manual
PSE2500-A3 External PoE
Power System

Chapter 5 Engineering

Maintenance and

Troubleshooting

5-2

Table 5-1 Troubleshooting guide

Controller

alarm

status

Rectifier

display

Possible

problems

Possible solution

RUN

ALM

NONE

z

The AC
power input
circuit
breakers
has
operated.

z

AC input
voltage is
too low or
power lost

z

Verify that AC power
input circuit breaker
is closed; close
circuit breaker if it is
open.

z

Verify the AC power
is present and in
normal range

RUN

ALM

AC OK

FAULT

Rectifier failure

Output beyond
normal range

Replace the rectifier

RUN

ALM

AC OK

DC OK

FAULT

Communication
error between
the rectifier and
the controller

Replace the rectifier

RUN

ALM

AC OK

Rectifier has no
output and it is
in standby
mode;

Over load;

Ambient
temperature is
too high

Rectifier failure;

Command the rectifier
to work or reset the
controller

Check if the load is over
the rating.

Check the ambient
temperature.

Replace the rectifier