Connecting to TCH A2 infrared heater
1. Infrared heater and control unit are designed to connect to the AC mains with 220V
single-phase voltage (allowable voltage uctuations from 198V to 242V).
2. To connect the control unit to the electric mains and a heater, unscrew 2 screws behind
the unit and remove the top cover.
3. The control unit is connected in compliance with the diagram, speci ed in Fig. 5, on the
case of an infrared heater and terminal block of the control unit.
4. The unit must be connected to the electric mains by the cable with strand cross section
not less than 1.5 mm2 and along with installation in the electric mains of a circuit breaker
with rated current not less than 16A.