Evaluation, Outputs – VEGA VEGABAR 20 User Manual

Page 19

Advertising
background image

VEGABAR 20

19

Set-up

Note:
- A modification of zero does not influence

the adjusted span.

- By pushing the “+“ and “–“-keys the output

current remains on the last value, after
saving with the “OK“-key, the output cur-
rent takes on the adjusted value.

Evaluation

Adjustment of the integration time

An integration time t

i

of 0 s … 10 s

can be adjusted with the “+“ or “–“-
key to damp pressure shocks. The
adjusted value can be saved with

the “OK“-key.

Selection of the unit

The actual measured pressure is
displayed on the DOT-matrix in the
measured value indication. The
appropriate unit can be chosen
from a list with the “+“ or “–“-key
and the “OK“-key. When choosing
the unit “Scal.“ the following menu
points are available.

Scaling

In operating condition the actual measured
pressure is displayed on the indicating mod-
ule:
- as a bar graph with 20 segments
- as a 4-digit digital value.

Bar graph and digital value relate to the ad-
justed measuring range and change propor-
tionally to the current output. Digital values
< –10 % or > 110 % are displayed as flash-
ing figures.

As a result of scaling, the 4 mA or 20 mA
user-specific current output values are as-
signed to the indicating module as 4-figure
digital values.

Outputs

Current output/Selection of the character-
istics

The current output provides the actual meas-
ured pressure as an analogue current signal
4 … 20 mA depending on the adjustment.

The characteristics can also be
inverted, i.e. adjusted to 20 ... 4 mA
with the “+“ or “–“-key and the
“OK“-key.

Fault signal

The fault signal is triggered via the current
output if during continuous self-monitoring,
failures, damage or interference in the mea-
suring cell or the electronics are detected, .

You choose whether the failure
current should be 22 mA or 3,6 mA
with the “+“ or “–“-key and the
“OK“-key .

Simulation

You can adjust with the “+“ or “–“-
key an individual pressure or %-
value to check the outputs of VEGA-
BAR and connected components.
The adjusted value flashes with
activated simulation. The simulation
can be finished with the “OK“-key.

ti

1

s

Unit

0,0

mbar

psi
kPa
%
scal.
mA

Scaling

indica-

tion

100%=

1000

Decimal

point

888,8

0%=

0

Escape

Fautl

signal

22mA

3,6mA

Current

output

4-20mA

20-4mA

Simula-

tion

Sim.

xx,x

mbar

Advertising