5 diagnosis, 1 maintenance, 2 failure removal – VEGA VEGABAR 20 User Manual

Page 21: Fault signals, Troubleshooting

Advertising
background image

VEGABAR 20

21

Diagnosis

5 Diagnosis

5.1 Maintenance

VEGABAR process pressure transmitters are
maintenance free.

5.2 Failure removal

Fault signals

VEGABAR provides high reliability with its
self-test and continuous self-monitoring. If
however malfunctions occur, VEGABAR diag-
nosis distinguishes between atypical proc-
ess conditions and faults in the VEGABAR.

Atypical process conditions

Exceeding or not reaching the measuring
range limits (fault signal extinguishes when
the value is again in the measuring range).

Failure in VEGABAR

Failure in the electronics, interferences or
damages in the measuring cell.

The following table assists in analysing the
fault signals.

Reason

Fault signal via

DOT-matrix

Bargraph

Current

Digital indication

output

Clearly

“OPERATE

Bargraph 0 %

outside

????

or 100 %

Current

measuring

bar“,

Digital value

value

range

no adjust-

flashes, tendency

3,6 mA

ment

indication

or

possible

active

>21,6 mA

Overload

Bargraph 0 %

range

or 100 %,

of the

for digital value

measuring

four segments

cell

flash

Failure in

“Defect“,

all segments

VEGABAR

no adjust-

flash

ment
possible, no
measuring
function

On instruments with menu-guided adjustment
with additional functions, possible reasons
are displayed under the menu point “Diagno-
sis no.“ in case of failure.

Diagnosis no.

Meaning

1

No frequency from C/f-converter

2

Frequency signal of the capacitor
outside the limit values

3

Frequency signal of the reference
capacitor outside the limit values

4

Frequency signal temperature outside
the limit values

7

Communication erro to EEPROM

9

Error in EEPROM CRC-checksum

Troubleshooting

If the indicated value does not correspond to
the level in the vessel or to the process pres-
sure, the following measures must be carried
out:
- check the pressure compensation (only

with overpressure measuring ranges)

- check the electrical connection.

Checking pressure compensation

Open the housing of VEGABAR. The meas-
ured value should not change. However if the
indicated value changes, compensation of
the atmospheric pressure is not ensured and
the measured value will be affected. Check
the breather facility on the VEGABAR-hous-
ing.

Advertising