Adjustment, Adjust pa output – VEGA VEGABAR 44 Profibus PA User Manual

Page 20

Advertising
background image

20

VEGABAR 44 (Profibus PA)

Adjustment

(only possible, if "%“ or "Lin%“ has been
chosen for the PA output)

Adjustment taking the current pres-
sure into account (live adjustment)

Live adjustment comprises two steps:
1 Adjustment of zero
2 Adjustment of span

1 Adjustment of zero

(e.g. process pressure zero or vessel
empty)

Set the percentage value to 0.0 %
with the "+“ or "–“ key. Then push the
"OK“ key.

2 Adjustment of span

(e.g. process pressure or vessel level max.)

Set the percentage value to 100 %
with the "+“ or "–“ key. Then push the
"OK“ key.

Note:

- A modification of zero does not influence

the adjusted span.

- Push “+” and “-” simultaneously for stand-

ard adjustment of zero/span. The value
jumps directly to 0 %/100 %.

- When pushing the "+“ or "–“ keys individu-

ally, the output current remains at the last
value, it takes on the adjusted value only
after saving with the "OK“ key.

- It is also possible to adjust currents for

partial fillings or partial pressures, e.g.
25 % and 75 %. VEGABAR then automati-
cally calculates the values for 0 % or 100 %
(only possible with a level difference
>3.3 %).

Zero

0,0

%

Span

100

%

Setup

Adjust PA output

As a standard feature, the PA output is set to
"Pressure“. This means that the DMU outputs
only a pressure value which cannot be
adjusted. If the DMU should output a level
value, the PA output must be set to "%“, if the
volume of a tank should be outputted, you
have to choose "Lin%“. Move with the arrow
and "OK“ key to the menu item "PA output“,
choose there the requested option with the
"+“ or "–“ key and saved with the "OK“ key.

Under "Scaling out.“ you can modifiy the
number values (min/max), the position of the
decimal point and the unit (with the "+“ or "–“
key the values can be modified, with the "OK“
key the adjustments are saved).

Adjust-

ment

Calcu-

lation

Operate

0.123

bar

Output

Scaling

out.

100

%=

1000

Decimal

point

888,8

0

%=

0

Escape

PA

output

Press.

%
Lin%

Unit

0,0

bar

Escape