VEGA VEGABAR 44 Profibus PA User Manual

Page 25

Advertising
background image

VEGABAR 44 (Profibus PA)

25

Here you can choose in which unit the adjust-
ment should be made (mbar, psi, kPa). Then
you enter the pressure values corresponding
to 0 % and 100 %. Then click to

OK

. The

adjustment is now finished.

Click in the window "Adjustment“ to

Zero/

Span

.

Then in the window "Zero/Span adjustment“,
you have to choose the type of adjustment. If
you want to carry out the "Adjustment without
taking the actual product into account“ (dry
adjustment), click to

no

, then to

OK

.

If you want to carry out the "Adjustment
taking the actual product into account“ (live
adjustment), click in this window to

yes

, then

to

OK

.

Choose the measurement loop in which you
want to make the parameter adjustment and
click to

OK

.

From the window "Instrument data parameter
adjustment“ you reach all submenus of the
sensor. To get familiar with the available
options, try out the buttons one after the
other. You always return to this window. To
carry out the adjustment, click the button

Adjustment

.

Sensor parameter adjustment – Adjust-
ment

Click to

Instrument data

, then to

Parameter

adjustment

.

Setup