5 Diagnostics

5.1 Maintenance

VEGABAR process pressure transmitters are
maintenance-free.

5.2 Failure rectification

Fault signals

VEGABAR provides maximum reliability
through its self-test and continuous self-
monitoring. If however malfunctions occur,
VEGABAR diagnosis distinguishes between
atypical process conditions and faults in the
VEGABAR.

Atypical process conditions

Exceeding or falling short of measuring
range limits (fault signal extinguishes when
the measured value is again in the measuring
range).

Failure in VEGABAR

Failure in the electronics, interference or
damage in the measuring cell.

The following table assists in analysis of fault
signals.

Reason

Fault signal via

DOT-matrix

Bar graph
Digital indication

Clearly

"OPERATE

Bar graph 0 %

outside

????

or 100 %

measuring

bar“,

digital value

range

no more

flashes, tendency

adjustment

indication

possible

active

Overload

Bar graph 0 %

range

or 100 %,

of the

for digital value

meas. cell

four segments
flash

Failure in

all segments

VEGABAR

flash

On instruments with menu-driven adjustment
with additional functions, the possible rea-
sons are displayed under the menu items
"Diagnosis-no.“ in case of failure.

Diagnosis-no.

Meaning

1

No frequency from C/f-converter

2

Frequency signal of the capacitor not
within the limit values

3

Frequency signal of the reference
capacitor not within the limit values

4

Frequency signal temperature not
within the limit values

7

Communication with EEPROM
disrupted

9

Error in EEPROM CRC-checksum

11

Process connection or electronics
module has been exchanged
(appears for approx. 20 s after
switching on for the first time after
exchange)

Troubleshooting

If the displayed value does not correspond
to the level in the vessel or to the process
pressure, the following measures must be
taken:
- check the pressure compensation (only

with gauge pressure measuring ranges)

- check the electrical connection.

Checking pressure compensation

Open the housing of VEGABAR. The meas-
ured value must not change. However if the
displayed value changes, compensation of
the atmospheric pressure is not ensured and
will lead to distortion of the measured value.
Check the breather on the VEGABAR
housing.