3 exchange of the hygienic form seal – VEGA VEGABAR 44 Profibus PA User Manual

Page 34

Advertising
background image

34

VEGABAR 44 (Profibus PA)

Instrument modification

6.3 Exchange of the hygienic form

seal

The ceramic measuring cell is sealed by a
gapless, radial form seal on VEGABAR 44
process pressure transmitter with hygienic
fitting. This form seal can be exchanged by
the user without readjustment being neces-
sary. The criteria and time periods for such
an exchange are defined by process condi-
tions and hygienic requirements.

Important:

Only use the original VEGA replacement part
as seal ring!

Note the following procedure when exchang-
ing the seal.

Removal procedure:

1

Pressure transmitter should be unpres-
surized (switch off process pressure or
empty vessel).

2

Loosen the hexagon head screw (46 mm
across flats) (1) by turning counter-
clockwise

Note!

The process connection (2) (i.e. compression
nut) must not be loosened!

3

Completely loosen pressure screw and
remove the pressure transmitter from the
process connection

Note:

Should the pressure transmitter turn by loos-
ening the pressure screw, it can be held by
the adapter (3) with a wrench (SW 46).

4

Slightly lift the form seal (5) (with a knife
or something similar) and loosen it from
the ceramic measuring cell

5

If the form seal (5) does not cover the
measuring cell, it should be carefully
removed from the process connection.

Installation procedure:

6

Pull a new form seal (5) over the measur-
ing cell (the conical end should point
towards the process connection!).

7

Insert the pressure transmitter carefully
into the process connection by turning
clockwise.

8

Tighten hexagon head screw (46 mm) (1)
to its fixed position (45 Nm).

9

Return the housing (4) of the pressure
transmitter to its original position

Exchange of the form seal is now finished.
Ensure appropriate disposal of the removed
seal.

1 Hexagon pressure screw
2 Process connection
3 Adapter
4 Housing
5 Form seal