VEGASWING 81A EXD and 83A EXD

27

b.Current value > 22 mA
- Check all connections and the connection line to the sensor .
- Should the red failure lamp still light, separate the sensor from the

connection line and connect instead a r esistor of 1 kW.

When the failure lamp extinguishes, the sensor will be defect. Check

the connected sensor .

- Should the failure lamp still light, connect the sensor again. Separate

the signal conditioning instrument from the connection line and con-
nect to the sensor input a r esistor of 1 kW.

- Should the failure lamp still light, the signal conditioning instrument will

be defect. In this case return the instrument for repair to VEGA.

- When the failure lamp extinguishes, there is probably a shortcircuit in

the connection line. Check the connection line to the sensor .

Malfunction during

After pushing the test key , the switching conditions do not occur in the

function test

correct sequence or the correct period, e.g. there is no full signal
provided.
- Measure the line resistance

When the line is high-resistance, you have to take appropriate meas-
ures to reach a standard resistance. E.g. check the terminals and
cable connections on corrosion.