VEGASON 54K … 56K

13

Technical data

1)

Similar to DIN 16 086, reference conditions acc. to IEC 770;
temperature 15°C … 35°C; moisture 45 % … 75 %; pressure 860 mbar … 1060 mbar.

2)

The adjustment time is the time, required by the sensor, to output the correct level after a quick level
change (with max. 10 % deviation).

Accuracy

1)

(typical values under reference conditions, all statements relate to the nominal measuring
range)

Characteristics

linear

Deviation in characteristics including

linearity, reproducibility and
hysteresis (determined by
limit point methods)

< 0.1 %

Linearity

better than 0.05 %

Average temperature coefficient of the

zero signal

0.06 %/10 K

Resolution in general

max. 1 mm

Resolution of the output signal

0.01 % or 1 mm

Characteristics

1)

(typical values under reference conditions, all statements relate to the nominal measuring
range)

Min. measuring range

(between empty and full adjustment)

> 20 mm (recommended > 50 mm)

Ultrasonic frequency (at 20°C)
- VEGASON 54

30 kHz

- VEGASON 55

18 kHz

- VEGASON 56

10 kHz

Measuring intervals
- VEGASON 54

1.0 s

- VEGASON 55

1.5 s

- VEGASON 56

2.0 s

Beam angle at -3 dB emitted power
- VEGASON 54

- VEGASON 55

- VEGASON 56

Influence of the process temperature

1.8 %/10 K, however is compensated by an
integral, dynamic temperature detection
system in the transducer

Influence of the process pressure

negligible within the approved sensor pressure
range

Adjustment time

2)

- VEGASON 54

> 2 s (depending on parameter adjustment)

- VEGASON 55, 56

> 4 s (depending on parameter adjustment)