Material cone, Mounting – VEGA Capacitive electrodes EL Profibus PA User Manual

Page 19

Advertising
background image

Capacitive electrodes EL - Profibus PA

19

d

d

d

6

d

6

Mounting

Filling

Emptying

Material cone, filling and emptying centered

d

3

1

2

d

10

Filling

Emptying

1 Emptying
2 Filling opening
3 Capacitive

electrode

Material cone, filling centered, emptying laterally

Material cone

When installing the meas. probe in a vessel,
be aware that conical heaps which alter the
switching point can form in solid materials.
We recommend selecting an installation loca-
tion where the electrode detects the average
value of the conical heap.

The measuring probe must be installed in a
way that takes the filling and emptying aper-
tures of the vessel into account. To compen-
sate measurement errors caused by the
conical heap, you should install the electrode
at a distance of approx.

d

/

6

from the vessel

wall.