5.4 Failure rectification

Failure

Measure, failure rectification

Sensor defective,

Test the internal connections:

measurement does

• Loosen the 4 screws of the housing cover with a Phillips screwdriver

and remove the housing cover.

not react to level
changes

• Loosen the two small screws with a Phillips screwdriver and pull the

no display of

oscillator out of the housing.

measured values

• Measure with an ohmmeter (range MOhm) the resistance values

between the following contacts:

C

M

- Capacitor

1 M

C

M

4

6

3

Screen

Contact 4 and middle pin (1)

The resistance must be 1 MOhm.
If the resistance is less, it indicates moisture in the housing or a defect
in the electrode insulation. A possible reason could be a non-insulated
electrode used in a conductive (moist) medium.
If the resistance is higher or if the connection is interrupted, the reason
is usually a bonding failure in the adapter plate or a resistor defective
due to strong electrostatic discharge.
In both cases, return the sensor to VEGA for repair.