VEGA Capacitive electrodes EL Profibus PA User Manual

Page 33

Advertising
background image

Capacitive electrodes EL - Profibus PA

33

Setup

Key

Display

Adjust-
ment

Para-
meter
adjust-
ment

Sensor

m(d)

4.700

OK

OK

with
medium

Min.
adjust
at %

-------

(Min. adjustment)

OK

OK

3. Conditioning

Under the menu item "

Signal conditioning" you

can scale the display, set an integration time
and choose a linearisation curve.

Scaling

Here, you can scale the digital display of the
electrode.

0 % correspond

Here, you enter the value which should be
displayed when 0 % level is reached, e.g.
20 l.

100 % correspond

Here, you enter the value which should be
displayed when 100 % level is reached, e.g.
1200 l.

If you need for the max. possible value a
number with more than four digits, then you
should choose the next higher unit, e.g.
14000 l = 140 hl.

Decimal point

If necessary, set the position of the decimal
point. Keep in mind that max. 4 digits can be
displayed.

Unit

In the menu "

Unit", you choose the physical

unit (%, t, ft

3

, in

3

, gal, in, lb, pF, m, cm, mm, ft,

yd, m

3

, kg, l, hl).

Linearisation curve

In the menu "

Lin. curve", you can choose

between three standard linearisation curves.
Preadjusted is a linear depedency between
percentage value of the level and the per-
centage value of the filling volume.

You can choose between linear, cylindrical
tank, spherical tank and user-programmable
linearisation curve. Programming your own
linearisation curve is only possible with the
PC and the adjustment program VVO. A
user-programmable curve, however, can be
transferred from the PC to the electronics of
the instrument and called up under this menu
item.

Integration time

In the menu item "

Integration time", you can

set a delay (in seconds) for the signal output.

4. Outputs

Under the menu "

Outputs", you can scale the

display and determine which parameter
should be outputted by the sensor display
and the PA output.

Advertising