VEGA VEGAPULS 51K…54K 4 … 20 mA; HART compact sensor User Manual

Page 54

Advertising
background image

54

VEGAPULS 51K … 54K

21750-EN-031222

1)

Similar to DIN 16 086, reference conditions acc. to IEC 770, e.g.
temperature 15 °C … 35 °C; moisture 45 % … 75 %; pressure 860 mbar … 1060 mbar

2)

The adjustment time (also actuating time, response time or adjustment period) is the time required by the
sensor to output the correct level (with max. 10% deviation) after a sudden level change.

3)

Average emitted power (electromagnetic energy) received by a body per cm² directly in front of the antenna.
The received emitted power depends on the antenna version and the distance.

Characteristics

1)

(typical values under reference conditions, all statements relate to the nominal measuring
range)

Min. span between

full and empty

> 10 mm (recommended > 50 mm)

Frequency

5.8 GHz (USA 6.3 GHz)

Intervals

- two-wire sensor (4 … 20 mA)

1 s

- four-wire sensor

0.5 s

Beam angle (at -3 dB)

- VEGAPULS 51 … 53

< 24°

- VEGAPULS 54

DN 80

38° (only suitable for standpipe measurement)

DN 100

30°

DN 150

20°

DN 200

16°

DN 250

14°

Adjustment time (response time)

2)

> 1 s (dependent on the parameter adjustment)

Influence of the process temperature

cannot be measured at 0 bar;
at 5 bar 0.004 %/10 °K;
at 40 bar 0.03 %/10 °K

Influence of the process pressure

0.0265 %/bar

Adjustment time

2)

> 1 s (dependent on the parameter adjustment)

Emitted radar power (average)

0.717 µW

Received average emitted power

3)

- distance 1 m

0.4 … 3.2 nW per cm² (0.4 … 3.2 x 10

-9

W/cm²)

- distance 5 m

0.02 … 0.13 nW per cm²

Connection cables

Two-wire sensors

power supply and signal via one
two-wire cable

Four-wire sensors

power supply and signal separated

Electrical connection

- spring-loaded terminals (max. 2.5 mm

2

)

- screwed connection

Cable entry

- ia terminal compartment

1 … 2 x M20 x 1.5 (cable-ø 5 … 9 mm) or
1 … 2 x ½“ NPT EEx d (cable-ø 3.1 … 8.7 mm
or 0.12 … 0.34 inch)

- Exd terminal compartment

(pressure-tight encapsulated)

1 x½“ NPT EEx d (cable-ø 3.1 … 8.7 mm or
0.12 … 0.34 inch)

Ground connection

max. 4 mm²

Technical data