Fig. 4: Temperature ranges
1

Process temperature

2

Ambient temperature

Danger:
I

nstruments in the version "Oil and grease free for oxygen" should be

unpacked just before mounting. After the protective cover of the
process fitting has been removed, the label "O₂" on the process fitting
is visible. Contamination by oil, grease and dirt should be avoided.
D

anger of explosion!

4.2 Mounting steps

F

or mounting VEGABAR 61, a welded socket is required. You can find

these components in the supplementary instructions manual "Welded
socket and seals
".

S

eal the thread with teflon, hemp or a similar resistant seal material on

the process fitting thread 1½ NPT.

à Screw VEGABAR 61 into the welded socket. Tighten the hexagon

on the process fitting with a suitable wrench. Wrench size, see
chapter "Dimensions".

Warning:
T

he housing must not be used to screw the instrument in! Applying

tightening force can damage internal parts of the housing.

S

eal the flange connections according to DIN/ANSI with a suitable,

resistant seal and mount VEGABAR 61 with suitable screws.

U

se the seal suitable for the respective process fitting. You can find

the components in the supplementary instructions manual "Welded
socket and seals
".

Oxygen applica-
tions

Welding the socket

Sealing/Screwing in
threaded versions

Sealing/Screwing in
flange versions

Sealing/Screwing in hy-
gienic fittings

14

VEGABAR

61 • 4 … 20

mA/HART

4 M

ounting

27519

-EN

-081209