o select the adjustment unit (in the example switching over from bar

to mbar) you have to proceed as follows:

3)

1

P

ush the [OK] button in the measured value display, the menu

overview is displayed.

B

asic adjustment

D

isplay

D

iagnostics

S

ervice

I

nfo

2

C

onfirm the menu "Basic adjustment" with [OK], the menu item

"U

nit" will be displayed.

U

nit

U

nit of measurement

bar

T

emperature unit

°C

3

A

ctivate the selection with [OK] and select "Units of measure-

ment

with [->].

4

A

ctivate the selection with [OK] and select the requested unit with

[->]

(

in the example mbar).

5

C

onfirm with [OK] and move to position correction with [->].

T

he adjustment unit is hence switched over from bar to mbar.

Information:
W

hen switching over to adjustment in a height unit (in the example

from bar to m), the density also has to be entered.

P

roceed as follows:

1

P

ush the [OK] button in the measured value display, the menu

overview is displayed.

2

C

onfirm the menu "Basic adjustment" with [OK], the menu item

"U

nits of measurement" will be displayed.

3

A

ctivate the selection with [OK] and select the requested unit with

[->]

(

in the example m).

4

C

onfirm with [OK], the submenu "Density unit" appears.

U

nit of measurement

D

ensity unit

kg/dm³

pcf

5

S

elect the requested unit, e.g. kg/dm³ with [->] and confirm with

[OK]

,

the submenu "Density" appears.

3)

S

election options: mbar, bar, psi, Pa, kPa, MPa, inHg, mmHg, inH

2

O,

mmH

2

O.

VEGABAR

61 • 4 … 20

mA/HART

35

6 S

et up with the indicating and adjustment module PLICSCOM

27519

-

EN

-081209