VEGA VEGABAR 61 4 … 20 mA_HART User Manual
Page 56
S
ignal resolution
1.6 µA
F
ailure signal current output (adjustable)
mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
M
ax. output current
22
mA
L
oad
see load diagram under Power supply
F
ulfilled NAMUR recommendations
NE
43
Dynamic behaviour output
R
un-up time approx.
10
s
90 %
100 %
10 %
t
t
T
A
t
t
S
2
1
Fig. 29: Sudden change of the process variable, dead time t
T
, rise time t
A
and step response time t
S
1
Process variable
2
Output signal
D
ead time
≤
150
ms
R
ise time
≤
100
ms (10 … 90 %)
S
tep response time
≤
250
ms (ti: 0 s, 10 … 90 %)
T
o this amounts the reaction time of the isolatng system. This time varies from values < 1 s with
compact isolating diaphragms up to several seconds with capillary systems.
E
xample: Flange isolating diaphragm DN 80, filling silicone oil KN 2.2, capillary length 10 m,
measuring range 1 bar
Process temperature
Reaction time
40 °C
approx. 2 s
20 °C
approx. 3 s
-20 °C
approx. 11 s
D
amping (63 % of the input variable)
0 … 999
s, adjustable
Input variable
Adjustment
56
VEGABAR
61 • 4 … 20
mA/HART
10 S
upplement
27519
-EN