VEGA VEGAPULS 43 4 … 20 mA; HART compact sensor User Manual
Page 53
VEGAPULS 43 – 4 … 20 mA
53
26626-EN-041227
Technical data
Accuracy
1)
(typical values under reference conditions, all statements relate to the nominal measuring
range, with VEGAPULS 45 relating to a nominal measuring range of 4 m)
Characteristics
linear
Accuracy
see diagram
Resolution, general
max. 1 mm
Resolution of the output signal
1.6 µA or 0.01 %
Ambient conditions
Vessel pressure
-100 … 1600 kPa (-1 … 16 bar)
Ambient temperature on the housing
- 4 … 20 mA two-wire sensor
-40°C … +80°C
- 4 … 20 mA four-wire sensor
-40°C … +80°C
- 4 … 20 mA four-wire sensor Ex d ia
-40°C … +60°C
Process temperature (flange temp.)
-40°C … +150°C
Storage and transport temperature
-60°C … +80°C
Protection
IP 66 and IP 67
Protection class
- two-wire sensor
II
- four-wire sensor
I
Overvoltage category
III
1)
Similar to DIN 16 086, reference conditions acc. to IEC 770, e.g.
temperature 15 °C … 35 °C; moisture 45 % … 75 %; pressure 860 mbar … 1060 mbar
0,5 m
30 m
10 mm
3 mm
-3 mm
-10 mm