VEGAPULS 43 – 4 … 20 mA

53

26626-EN-041227

Technical data

Accuracy

1)

(typical values under reference conditions, all statements relate to the nominal measuring
range, with VEGAPULS 45 relating to a nominal measuring range of 4 m)

Characteristics

linear

Accuracy

see diagram

Resolution, general

max. 1 mm

Resolution of the output signal

1.6 µA or 0.01 %

Ambient conditions

Vessel pressure

-100 … 1600 kPa (-1 … 16 bar)

Ambient temperature on the housing

- 4 … 20 mA two-wire sensor

-40°C … +80°C

- 4 … 20 mA four-wire sensor

-40°C … +80°C

- 4 … 20 mA four-wire sensor Ex d ia

-40°C … +60°C

Process temperature (flange temp.)

-40°C … +150°C

Storage and transport temperature

-60°C … +80°C

Protection

IP 66 and IP 67

Protection class

- two-wire sensor

II

- four-wire sensor

I

Overvoltage category

III

1)

Similar to DIN 16 086, reference conditions acc. to IEC 770, e.g.
temperature 15 °C … 35 °C; moisture 45 % … 75 %; pressure 860 mbar … 1060 mbar

0,5 m

30 m

10 mm

3 mm

-3 mm

-10 mm