4 technical data – VEGA VEGATRENN 544 Ex User Manual

Page 5

Advertising
background image

VEGATRENN 544 Ex

5

1.4 Technical data

Power supply

Operating voltage

U

nenn

= 24 V AC (20 … 53 V), 50/60 Hz
= 24 V DC (20 … 72 V)

Power consumption

appr. 7 VA or appr. 5 W

Measuring data input

Number

1 input

Kind of input

active two-wire input, analogue

Range

4 … 20 mA

Sensor

hydrostatic pressure transmitter,
process pressure transmitter,
differential pressure transmitter

Voltage

at 4 mA ca. 18 V DC, at 20 mA appr. 15 V DC

Current limitation

at appr. 26 mA, shortcircuit proof

Detection line break

< 2 mA

Detection shortcircuit

> 23 mA

Connection line

2-wire (standard line)

Resistance per conductor

max. 35

Resolution

1

µ

A

Linearity error

0,025 % at 4 … 20 mA

Temperature error

0,04 %/10 K at 4 … 20 mA

Measuring data input, Ex-technical data

Classification

[EEx ia] IIC, [EEx ia] IIB, [EEx ib] IIC or [EEx ib] IIB

Max. values
- Voltage

U

O

= 20 V

- Current

I

O

= 128 mA

- Power

P

O

= 640 mW

Characteristics

linear

Effective inner inductance L

i

negligible

Effective inner capacitance C

i

negligible

EEx ia IIC

EEx ia IIB

EEx ib IIC

EEx ib IIB

Max. permissible outer inductance L

O

(mH)

0,5 1

1,5

2

2

9

Max. permissible outer capacitance C

O

(nF)

97

78

68

486

200

1000

The intrinsically safe circuits are reliably separated from the not-intrinsically safe circuits up to a peak value of

the nominal voltage of 375 V.
The max. voltage on the not-intrinsically safe circuits must not exceed 250 V

eff

in case of failure.

Current output

Number

1 output

Function

analogue output of processing results

Range

0/4 … 20 mA

Load

max. 500

Resolution

0,05 % of range

Linearity error

0,05 % of range

Temperature error

0,05 %/10 k of range

Product description

>>

Advertising