VEGATRENN 544 Ex

9

Mounting

Ex-version

Note!

VEGATRENN must be generally mounted outside

hazardous areas or special Ex-protective measures
must be taken.

Ex-separating chamber

To ensure suffcient "air and creeping distances", an

Ex-separating chamber must be mounted to the
connections of VEGATRENN. Loop the wires through
the Ex-separating chamber and connect them. Fasten
the Ex-separating chamber with the lower screw.
Observe the operating instruction of carrier

BGT 596 Ex.M.

Protection for Ex-applications

In Ex-applications a protection of IP 20 must be kept.
Cover the spaces or not used modules from the front

by appropriate blind covers.

Mounting in carriers

If you mount your VEGATRENN with Ex-approval in a
carrier, you have to use a VEGA-Ex-module. Keep a

distance of at least 10 mm (2 TE) to modules of other
manufacturers. If you want to mount the VEGATRENN
in the extreme left position in the carrier, you have to
mount a blind cover of at least 20 mm (4 TE) in front of
the module of the instrument.

Blind cover

on

VEGATRENN

544 Ex

8

7

6

5

4

0

F

E

D

C

B

A

9

3 3

2

1

2.2 Instrument address

Adjust on the respective switch on the circuit board
the instrument address. Address range 1 … 15. Ob-
serve that no double coordination is made. Factory
setting = instrument address 0

corresp.

10

11

12

13

14

15