2 Mounting

2.1 Mounting versions

VEGATRENN 544 Ex separator can be either mounted
with a module in a carrier BGT 596 Ex.M or in a single
housing type 505.

Module Ex

Multipoint connector DIN 41 612, series F, 33-pole (d,
b, z) with coded pins, Ex-separating chamber and
mounting material for mounting in carrier
BGT 596 Ex.M.

Single housing

Plastic housing type 505 for single mounting.

Mounting carrier

Mount the respective module (Ex-version) in the
carrier. Wire the connections of the multipoint connec-

tor according to the wiring plan on the following
pages.

The multipoint connector is available as follows:
- Wire-Wrap standard connection 1,0 x 1,0 mm

- plug connection 2,8 x 0,8 mm
- Termi-Point Standard connection 1,6 x 0,8 mm
- soldering connection
- screw terminals 2 x 0,5 mm

2

For further information concerning mounting see

operating instruction of the carrier.

Mounting single housing

You can either screw the housing socket directly to the
mounting plate or plug on a carrier rail (TS 35 x 7,5
acc. to EN 50 022 or TS 32 acc. to EN 50 035). Con-
nect the terminals according to the wiring plan on the

following pages. For further information to mounting
see operating instruction of the housing.

Transparent cover

To protect the housing against unauthorized operation,
the front plate of VEGATRENN can be provided with a
lockable transparent cover.

Coding

To avoid interchanging of the various signal condition-
ing instruments, the multipoint connector of the carrier
or the housing is provided with pins and the multiple

plug of VEGATRENN with holes (mechanical coding).

An Ex-coding with fixed coded pin ensures that not-Ex
and Ex-instruments are not interchanged.

An instrument coding ensures that the various signal
conditioning instruments are not interchanged. The
respective coded pins are attached to each module or
housing. Provide the multipoint connector with these
coded pins acc. to the following schedule and figure.

Instrument

Ex-

coding

coding

VEGAMET 514 D

a5 / c5

VEGAMET 514 D Ex

a5 / c5

c23

VEGAMET 514 VD

a7 / c5

Fig. 2.1 Coding schedule

Instrument coding

Function coding

o 9 o

z b d

o 1 o

a c

a1

c23

o 3 o

o 5 o

o 7 o

o11o

o13o

o15o

c5

o17o

o19o

o21o

o23o

o25o

o27o

o29o

o31o

VEGATRENN

Ex-coding

544

Fig. 2.2 Module coding, VEGATRENN