Pressure transmitter D96/D97 (Profibus PA)

31

Diagnostics

5 Diagnostics

5.1 Maintenance

Pressure transmitter D96 and D97 are main-
tenance-free.

5.2 Failure rectification

Fault signals

The pressure transmitter D96/D97 provides
maximum reliability through its self-test and
continuous self-monitoring. If, however, mal-
functions occur, the pressure transmitter
D96/D97 diagnosis distinguishes between
atypical process conditions and faults in the
pressure transmitter D96/D97.

Atypical process conditions

Exceeding or falling short of measuring
range limits (fault signal extinguishes when
the measured value is again in the measuring
range).

Failure in the D96/D97 pressure transmit-
ter

Failure in the electronics, interference or
damage in the measuring cell.

The following table assists in the analysis of
fault signals.

Cause of

Fault signal via

failure

DOT-matrix

Bar graph
Digital indication

Clearly

"OPERATE

Bar graph 0 %

outside

????

or 100 %

measuring

bar"

digital value

range

flashes

Overload

Bar graph 0 %

range

or 100 %,

of the

digital value

meas. cell

four segments

flash "- - - -"

Failure in

all segments

D96/D97

flash

On instruments with menu-driven adjustment
with additional functions, the possible causes
are displayed under the menu item "Diagnos-
tics no." in case of failure.

Diagnostics

Meaning

no.

1

No frequency from C/D-converter

2

Frequency signal of the capacitor not
within the limit values

3

Frequency signal of the reference
capacitor not within the limit values

4

Frequency signal temperature not
within the limit values

7

Communication with EEPROM dis-
rupted

9

Error in EEPROM CRC-checksum

11

Process connection or electronics
module has been exchanged (ap-
pears for approx. 20 s after switching
on for the first time after exchange)

Troubleshooting

If the displayed value does not correspond
to the level in the vessel or to the process
pressure, the following measures must be
taken:
- check the pressure compensation (only

with gauge pressure measuring ranges)

- check the electrical connections.

Checking pressure compensation

Open the processing unit of the pressure
transmitter. The measured value must not
change. However, if the displayed value
changes, compensation of the atmospheric
pressure is not ensured, which can result in
distortion of the measured value. Check the
breather on the processing unit.