32

Pressure transmitter D96/D97 (Profibus PA)

Instrument modification

6 Instrument modification

6.1 Exchange of adjustment mod-

ules in the processing unit

The modular construction of the processing
unit allows retrofitting, interchange and re-
moval of the adjustment modules and the
display module. Data previously saved (e.g.
adjustment values) are not stored in the ad-
justment module but in an EEPROM of the
electronics module and readjustment is
therefore not necessary. The connection of
the modules is made via a 4-pole plug con-
nection.

Exchange of the adjustment module

Removal of the adjustment module

Separate processing unit from the power
supply.

Remove the screws on the upper side of
the housing and remove the cover or the
display module.

Disconnect the cables from the terminals,
and if applicable, pull out the plug con-
nection of the display module.

Remove the two screws of the adjustment
module.

Remove adjustment module and pull out
plug connection.

Insertion of an adjustment module

Plug the plug connection of the new ad-
justment module into the plug-in socket of
the electronics module.

Fasten the new adjustment module.

Reconnect the cables, and if applicable,
also the cable from the display module.

Replace the cover or the display module
of processing unit.

Reconnect processing unit to power
supply.

Processing unit

Module without
adjustment

Module for
menu-driven
adjustment

Display
module