VEGA VEGAFLEX 55P (Profibus PA) User Manual

Page 29

Advertising
background image

VEGAFLEX 55P (Profibus PA)

29

Setup

2. Conditioning

Under the menu item "

Conditioning", you

choose the distance at 0 % and at 100 %
filling. Then you enter the physical quantity
and the unit as well as the decimal point.
• Enter in the menu window "

0 % corre-

spond" the value of the 0 % filling. This will
be e.g. "80" for 80 liters.

• Confirm with "

OK".

• With the arrow key, you switch to the 100 %

menu. Enter here the value of your param-
eter corresponding to a 100 % filling. E.g.
"1200" for 1200 liters.

• Confirm with "

OK".

• If necessary, choose a decimal point. Note

that max. 4 digits can be shown.

• In the menu "

prop. to", you choose the

parameter (mass, volume, distance…),

• In the menu "

Unit", you choose the physical

unit (kg, l, ft

3

, gal, m

3

…).

• With the "ESC" key, you go back to the next

higher menu level. With the arrow key, you
choose the next menu item.

• In the menu

"Lin. curve", you can choose

between three standard linearisation
curves.
A linear correlation between the
percentage value of the product distance
and the percentage value of the filling
volume has been preset.
You can choose between linear, spherical
and cylindrical tank. Entering a user-pro-
grammable curve is only possible with the
PC and the adjustment program VVO.

• In the menu item

"Integration time", you can

set a delay period for the signal output.

3. Outputs

Under the menu "

Outputs“ you can scale the

display and determine which parameter
should be indicated on the sensor display.

4. Operating range

Without special adjustment, the operating
range corresponds to the measuring range.
The measuring range is automatically set with
the min./max. adjustment. It is generally
better to set a slightly wider span for
operating range (approx. 5 %) than for the
measuring range (meas. span).

Example:
Min./Max. adjustment: 0.300 … 5.850 m; set
operating range to approx. 0.250 … actual
rod length.

5. Meas. conditions

With these functions, you can enter the ambi-
ent conditions in the vessel (see menu sche-
matic).

6. Useful level and noise level

In the menu

"Info", you get important informa-

tion on the signal quality of the product echo.
The higher the "

S-N" value, the more reliable

the measurement.

Ampl.: Means amplitude of the product echo

in dB (useful signal level)

S-N:

Means Signal-Noise (useful signal
level minus noise level)

The higher the S-N value (useful signal
level minus noise level), the higher the reliabil-
ity:
> 30 dB

Measurement good

10 … 30 dB

Measurement satisfactory

< 10 dB

Measurement bad

Advertising