2 profibus pa – VEGA VEGACAL 63 Profibus PA User Manual

Page 43

Advertising
background image

43

10 Supplement

VEGACAL 63 • Profibus PA

30028-EN-130917

Electrical protective measures
Protection, depending on housing version

Ʋ Plastic housing

IP 66/IP 67

Ʋ Aluminium housing, stainless steel

housing - investment casting, stain-

less steel housing - electro-polished

IP 66/IP 68 (0.2 bar)

3)

Ʋ Aluminium and stainless housing, in-

vestment casting (optionally available)

IP 66/IP 68 (1 bar)

Overvoltage category

III

Protection class

II

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully

noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools"

and "serial number search" as well as via "Downloads" and "Approvals".

10.2 Profibus PA

Instrument master file

The instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.

These data are, e.g. the permissible transmission rates as well as information on diagnostics values

and the format of the measured value outputted by the PA instrument.
A bitmap file is also provided for the Profibus network planning tool. This file is installed automati-

cally when the GSD file is integrated. The bitmap file is used for symbolic indication of the PA instru-

ment in the configuration tool.

Ident number

Each Profibus instrument gets an unambiguous ident number (ID number) from the Profibus user

organisation (PNO). This ID number is also included in the name of the GSD file. For VEGACAL 63

the ID number is 0x076E(hex) and the GSD file CL__076E.GSD. Optionally to this manufacturer-

specific GSD file, PNO provides also a general so-called profile-specific GSD file. For VEGACAL 63

you have to use the general GSD file PA139700.GSD. If the general GSD file is used, the sensor

must be set to the profile-specific ident number via the DTM software. By default, the sensor oper-

ates with the manufacturer-specific ID number.

Cyclical data traffic

The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during opera-

tion. The below block diagram below shows which data can be accessed by the PLC.