10 Supplement

VEGACAL 63 • Profibus PA

30028-EN-130917

Status

code

Description according to

Profibus standard

Possible cause

0x44

uncertain - last unstable value

Failsafe replacement value (Failsafe-Mode = "Last value" and al-

ready valid measured value since switching on)

0x48

uncertain substitute set

– Switch on simulation

– Failsafe replacement value (Failsafe-Mode = "Fsafe value")

0x4c

uncertain - initial value

Failsafe replacement value (Failsafe-Mode = "Last valid value" and

no valid measured value since switching on)

0x51

uncertain - sensor; conversion

not accurate - low limited

Sensor value < lower limit

0x52

uncertain - sensor; conversion

not accurate - high limited

Sensor value > upper limit

0x80

good (non-cascade) - OK

OK

0x84

good (non-cascade) - active

block alarm

Static revision (FB, TB) changed (10 sec. active, after the parame-

ter of the static category has been written)

0x89

good (non-cascade) - active ad-

visory alarm - low limited

Lo-Alarm

0x8a

good (non-cascade) - active ad-

visory alarm - high limited

Hi-Alarm

0x8d

good (non-cascade) - active crit-

ical alarm - low limited

Lo-Lo-Alarm

0x8e

good (non-cascade) - active crit-

ical alarm - high limited

Hi-Hi-Alarm