2 setup procedure, two–wire electronics – VEGA VEGAPULS series 60 Electronics module (≥ 2.0.0 - ≤ 3.8) User Manual

Page 14

Advertising
background image

Load this file with "Save target as" on your PC. Start

PACTware™ and mode in the Service-DTM to the menu item

"Electronics exchange". Transfer the XML file into the sensor.

5.2 Setup procedure, two-wire electronics

As a rule, all settings already carried out on site with the

previous electronics module such as min./max. adjustment,

false echo fade-out etc., must be repeated.

Tip:

For this purpose, use the copy function of the indicating and

adjustment module or the adjustment software PACTware™.

5.3 Setup steps four-wire electronics 4 … 20 mA/

HART

With four-wire instruments 4 … 20 mA/HART there is a power

supply electronics in the connection compartment. This

electronics is used for connection to the voltage supply and

delivers the 4 … 20 mA output current. The electronics module

must be adapted to the power supply electronics after an

exchange.
Proceed as follows:
1 Connecting the sensor to voltage supply
2 Connect the PC with PACTware™ via VEGACONNECT 3

to the sensor

3 Connect ammeter with measuring range 20 mA as well as

resolution and accuracy ≤1 µA to the current output

4 Select in the Service-DTM the menu item "Current

calibration" and start the calibration

Information:

The electronics module starts a calibration procedure and

simulates two current values. These values are influenced by

the power supply electronics and displayed on the ammeter.

Typical values are e.g. 6819 and 18597 µA.

5 Enter the measured current values for the first and second

calibration point into the respective menu items.

The Service-DTM confirms the successful input of the current

values and indicates the actual current value. This value

corresponds to the actual measured value taking the calibra-

tion into account.