4 mount, 1 general instructions – VEGA VEGAPULS series 60 Electronics module (≥ 2.0.0 - ≤ 3.8) User Manual

Page 6

Advertising
background image

4 Mount

4.1 General instructions

If the electronics module is defective, it can be replaced by the

user.

In Ex applications, only an instrument and an electronics

module with appropriate Ex approval may be used.

If there is no electronics module available on site, one can be

ordered from the VEGA agency serving you.

The new electronics module must be loaded with the order and

factory data of the sensor. These are the options:

l

at the factory by VEGA

l

or on site by the user

Information:

When loading on site, first of all the order data must be

downloaded from the Internet (see "Setup").

In both cases, the sensor serial number is necessary. The

serial numbers are stated on the type label of the instrument,

inside the housing or on the delivery note.

Caution:

The order data and company data contain important preset-

tings for the sensor. A reliable operation and a correction of the

measurement is not possible without these data.

Electronics modules are adapted to the respective sensor.

They differ, e.g. in the signal output, the power supply or

approval.
First of all check by means of the overview in section Mounting

preparations, if you are using the suitable electronics module.

Compare the new electronics module with the existing one.

The specifications on the type label must correspond. This

applies mainly to instruments with approvals.

Warning:

Switch off voltage supply before starting the mounting

procedure. The replacement electronics must only be mounted

in idle condition. Non-observance will damage the elec-

tronics!

Sensor serial number

Assignment

6

Electronics module - VEGAPULS series 60

Mount

30176

-EN
-070220

Advertising