VEGA VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) standpipe ver. 4 … 20 mA_HART four-wire User Manual

Page 25

Advertising
background image

I

n the main menu item "Basic adjustment", the individual submenu

items should be selected one after the other and provided with the
correct parameter values.

S

tart your parameter adjustment with the following menu items of the

basic adjustment:

P

roceed as follows:

1

M

ove from the measured value display to the main menu by

pushing [OK].

B

asic adjustment

D

isplay

D

iagnostics

S

ervice

I

nfo

2

S

elect the menu item "Basic adjustment" with [->] and confirm with

[OK]

. N

ow the menu item "Min. adjustment" is displayed.

M

in. adjustment

0.00 %

=

5.000 m(d)

4.000

m(d)

3

P

repare the % value for editing with [OK] and set the cursor to the

requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.

4

E

nter the suitable distance value in m for the empty vessel (e.g.

distance from the sensor to the vessel bottom) corresponding to
the percentage value.

5

S

ave the settings with [OK] and move to "Max. adjustment" with [-

>

]

.

P

roceed as follows:

M

ax. adjustment

100.00 %

=

1.000 m(d)

2.000

m(d)

1

P

repare the % value for editing with [OK] and set the cursor to the

requested position with [->]. Set the requested percentage value
with [+] and save with [OK]. The cursor jumps now to the distance
value.

2

E

nter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. Keep in mind that the max.
level must lie below the dead band.

Carrying out min. ad-
justment

Carrying out max. ad-
justment

VEGAPULS

62

standpipe version • 4 … 20 mA/HART four-wire

25

6 S

et up with the indicating and adjustment module PLICSCOM

28738

-EN

-090305

Advertising