T

his function enables reading out parameter adjustment data as well

as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".

T

he following data are read out or written with this function:

l

M

easured value presentation

l

A

djustment

l

M

edium

l

I

nner diameter of the standpipe (with standpipe versions)

l

V

essel form

l

D

amping

l

L

inearisation curve

l

S

ensor-TAG

l

D

isplayed value

l

D

isplay unit

l

S

caling

l

C

urrent output

l

U

nit of measurement

l

L

anguage

T

he following safety-relevant data are not read out or written:

l

HART

mode

l

PIN

l

SIL

C

opy sensor data

C

opy sensor data?

Basic adjustment
I

f the "Reset" is carried out, the sensor resets the values of the

following menu items to the reset values (see chart):

1)

Menu item

Reset value

M

ax. adjustment

0

m(d)

M

in. adjustment

30

m(d) (VEGAPULS 61, 63, 65, 67)

35

m(d) (VEGAPULS 62, 66)

70

m(d) (VEGAPULS 68)

M

edium

L

iquid

V

essel form

not known

D

amping

0

s

L

inearisation

linear

S

ensor-TAG

S

ensor

D

isplayed value

D

istance

E

xtended settings

N

one

1)

S

ensor-specific basic adjustment.

Copy sensor data

Reset

28

VEGAPULS

62

standpipe version • 4 … 20 mA/HART four-wire

6 S

et up with the indicating and adjustment module PLICSCOM